5.3.2 Grounding for EMC-Compliant Installation
•
Establish electrical contact between the cable shield and the enclosure using the I/O shielding plate on each module.
1
2
3
e
3
0
b
g
8
0
5
.1
0
1 Cable
3 I/O shielding plate
2 Cable tie
Illustration 38: Cable Shielding on the Top of the System Components
1
2
3
e3
0b
h3
43
.1
0
1 Cable tie
3 PE screw
2 EMC metal shielding plate
Illustration 39: Cable Shielding on the Bottom of the System Components
•
Use a cable with a shielding that has a high-coverage to reduce electrical interference.
•
Do not use pigtails to connect the shielding. A 360° wire connection is recommended.
Electrical Installation
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
60 | Danfoss A/S © 2019.10
Содержание VLT MSD 510
Страница 1: ...Operating Guide VLT Multiaxis Servo Drive MSD 510 System...
Страница 2: ......