selections, fault log, alarm log, and other
monitoring functions.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure, via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
parameter 14-22 Operation Mode
and
press [OK].
3.
Scroll to
[2] Initialisation
and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until a click is heard and
the fan starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
frequency converter information:
•
Parameter 15-00 Operating hours
•
•
•
3.2 Basic Programming
3.2.1 Asynchronous Motor Set-up
Enter the following motor data. Find the information on
the motor nameplate.
1.
Parameter 1-20 Motor Power [kW]
.
2.
Parameter 1-22 Motor Voltage
.
3.
Parameter 1-23 Motor Frequency
.
4.
Parameter 1-24 Motor Current
.
5.
Parameter 1-25 Motor Nominal Speed
.
For optimum performance in VVC
+
mode, extra motor data
is required to set up the following parameters. The data is
found in the motor datasheet (this data is typically not
available on the motor nameplate). Run a complete AMA
using
parameter 1-29 Automatic Motor Adaptation (AMA)
[1]
Enable Complete AMA
or enter the parameters manually.
1.
Parameter 1-30 Stator Resistance (Rs)
.
2.
Parameter 1-31 Rotor Resistance (Rr)
.
3.
Parameter 1-33 Stator Leakage Reactance (X1)
.
4.
Parameter 1-35 Main Reactance (Xh)
.
Application-specific adjustment when running VVC
+
VVC
+
is the most robust control mode. In most situations,
it provides optimum performance without further
adjustments. Run a complete AMA for best performance.
3.2.2 PM Motor Set-up in VVC
+
Initial programming steps
1.
Set
parameter 1-10 Motor Construction
to the
following options to activate PM motor operation:
1a
[1] PM, non salient SPM
1b
[2] PM, salient IPM, non Sat
1c
[3] PM, salient IPM, Sat
2.
Select
[0] Open Loop
in
parameter 1-00 Configu-
ration Mode
.
NOTICE
Encoder feedback is not supported for PM motors.
Programming motor data
After selecting 1 of the PM motor options in
parameter 1-10 Motor Construction
, the PM motor-related
parameters in parameter groups
1-2* Motor Data
,
1-3* Adv.
Motor Data
, and
1-4* Adv. Motor Data II
are active.
Find the information on the motor nameplate and in the
motor data sheet.
Program the following parameters in the listed order:
1.
Parameter 1-24 Motor Current
.
2.
Parameter 1-26 Motor Cont. Rated Torque
.
3.
Parameter 1-25 Motor Nominal Speed
.
4.
Parameter 1-39 Motor Poles
.
5.
Parameter 1-30 Stator Resistance (Rs)
.
Enter line-to-common stator winding resistance
(Rs). If only line-line data is available, divide the
line-line value by 2 to achieve the line-to-
common (starpoint) value.
It is also possible to measure the value with an
ohmmeter, which also takes the resistance of the
cable into account. Divide the measured value by
2 and enter the result.
6.
Parameter 1-37 d-axis Inductance (Ld)
.
Programming
VLT
®
Midi Drive FC 280
20
Danfoss A/S © 12/2015 All rights reserved.
MG07C102
3
3