Power [kW (hp)]
Height [mm (in)]
Width [mm (in)]
Depth
[mm (in)]
(1)
Maxi-
mum
weight
M5
–
18.5–22.0 (25–
30)
335 (13.2) 387.5 (15.3)
315 (12.4) 165 (6.5) 140 (5.5) 248 (9.8)
9.1
1
For LCP with potentiometer, add 7.6 mm (0.3 in).
3.4 Tightening of Terminals
N O T I C E
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conduc-
tors required, 60–75 °C (140–167 °F) recommended.
Table 3: Tightening of Terminals
Power [kW (hp)]
Torque [Nm (in-lb)]
Enclo-
sure
1x200–240 V
3x380–480 V
Line
Motor
DC connection/
brake
Control termi-
nals
Ground Relay
M1
0.18–0.75
(0.24–1.0)
0.37–0.75
(0.5–1.0)
0.8 (7.1)
0.7 (6.2)
Spade
(1)
0.15 (1.3)
3 (26.6)
0.5 (4.4)
M2
1.5 (2.0)
1.5–2.2 (2.0–3.0)
0.8 (7.1)
0.7 (6.2)
Spade
(1)
0.15 (1.3)
3 (26.6)
0.5 (4.4)
M3
2.2 (3.0)
3.0–7.5 (4.0–10)
0.8 (7.1)
0.7 (6.2)
Spade
(1)
0.15 (1.3)
3 (26.6)
0.5 (4.4)
M4
–
11.0–15.0 (15–20) 1.3 (11.5) 1.3 (11.5) 1.3 (11.5)
0.15 (1.3)
3 (26.6)
0.5 (4.4)
M5
–
18.5–22.0 (25–30) 1.3 (11.5) 1.3 (11.5) 1.3 (11.5)
0.15 (1.3)
3 (26.6)
0.5 (4.4)
1
Spade connectors (6.3 mm (0.25 in) Faston plugs).
3.5 Fuses
3.5.1 Branch Circuit Protection
To prevent fire hazards, protect the branch circuits in an installation, switch gear, machines, and so on, against short circuits and
overcurrent. Follow national and local regulations.
3.5.2 Short-circuit Protection
Use the Danfoss recommended fuses to protect service personnel or other equipment if there is an internal failure in the unit or
short circuit on DC-link. If there is a short circuit on the motor or brake output, the drive provides full short-circuit protection.
3.5.3 Overcurrent Protection
To avoid overheating of the cables in the installation, provide overload protection. Always carry out overcurrent protection accord-
ing to national regulations. Fuses must be designed for protection in a circuit capable of supplying a maximum of 100000 A
rms
(symmetrical), 480 V maximum.
3.5.4 Non-UL Compliance
If UL/cUL is not to be complied with, use the fuses mentioned in this chapter, which ensure compliance with EN50178/IEC61800-5-1.
If there is a malfunction, not following the fuse recommendation may result in damage to the drive and the installation.
AQ348848915086en-000101 / 130R0943
10 | Danfoss A/S © 2020.09