Troubleshooting
Contact the local Danfoss supplier for advice.
There are no parameters relatedto this trip message.
11.2.55 Zero Speed Detect
Cause
The zero-speed detect input has not closed within the expected duration of a soft stop.
Troubleshooting
Check that the zero-speed sensor is operating correctly.
Check that
parameter 2-17 Brake Current Limit
and
parameter 5-15 Excess Start Time
are appropriate for the application.
Check the following parameters:
Parameter 2-17 Brake Current Limit
.
Parameter 3-19 Brake Current Limit-2
.
Parameter 5-15 Excess Start Time
.
11.3 General Faults
Table 215: General Faults
Symptom
Probable cause/suggested solution
"Not ready" on dis-
play
The reset input may be active. If the reset input is active, the soft starter does not operate.
Simul
on display
The soft starter is running simulation software. This software is intended for demonstration purposes on-
ly and is not suitable for controlling a motor. Contact the local supplier for advice.
The soft starter does
not respond to the
[Hand on] and [Re-
set] keys.
The soft starter only accepts commands from the LCP if
parameter 1-1 Command Source
is set to
Remote
LCP
. Check that the Local LED on the soft starter is on.
The soft starter does
not respond to com-
mands from the con-
trol inputs.
The soft starter only accepts commands from the inputs if
parameter 1-1 Command Source
is set to
Digital Input
. Check the setting of
parameter 1-1 Command Source
.
The control wiring may be incorrect. Check that the remote start, stop, and reset inputs are config-
ured correctly (see
) for details.
The signal to the remote inputs may be incorrect. Test the signaling by activating each input signal in
turn.
The soft starter does
not respond to a
start command from
either the LCP or the
digital inputs.
The soft starter may be waiting for the restart delay to elapse.
Parameter 5-16 Restart Delay
controls
the length of the restart delay.
The motor may be too hot to allow a start. The soft starter only allows a start when it calculates that
the motor has sufficient thermal capacity to complete the start successfully. Wait for the motor to
cool, before attempting another start.
The reset input may be active. If the reset input is active, the soft starter does not operate.
The soft starter may be waiting for control signals via the communications network (
parameter 1-1
Command Source
set to
Network
).
The soft starter may be waiting for a scheduled auto-start (
parameter 1-1 Command Source
set to
Clock
).
Erratic and noisy mo-
tor operation
If the soft starter is connected to the motor using inside delta configuration, the soft starter may not be
detecting the connection correctly. Contact the local supplier for advice.
AQ262141844215en-000401 / 175R1174 | 129
Danfoss A/S © 2020.12
Troubleshooting
VLT® Soft Starter MCD 600
Operating Guide
Содержание VLT MCD 600
Страница 1: ...Operating Guide VLT Soft Starter MCD 600 vlt drives danfoss com...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 6: ......
Страница 139: ...AQ262141844215en 000401 175R1174 135 Danfoss A S 2020 12 Index VLT Soft Starter MCD 600 Operating Guide...