Illustration 5.15: Cable entry holes for enclosure C2. The suggested use of the holes are purely recommendations and other solutions are
possible.
Legend:
A: Line in
B: Brake/load sharing
C: Motor out
D: Free space
5.2.6 Removal of Knockouts for Extra Cables
1.
Remove cable entry from the frequency converter (Avoiding foreign parts falling into the frequency converter when removing knockouts)
2.
Cable entry has to be supported around the knockout you intend to remove.
3.
The knockout can now be removed with a strong mandrel and a hammer.
4.
Remove burrs from the hole.
5.
Mount Cable entry on frequency converter.
5.2.7 Gland/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12)
Cables are connected through the gland plate from the bottom. Remove the plate and plan where to place the entry for the glands or conduits. Prepare
holes in the marked area on the drawing.
NB!
The gland plate must be fitted to the frequency converter to ensure the specified protection degree, as well as ensuring proper cooling
of the unit. If the gland plate is not mounted, the frequency converter may trip on Alarm 69, Pwr. Card Temp
VLT
®
HVAC Drive Design Guide
5 How to Install
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
93
5
Содержание VLT HVAC
Страница 50: ...3 VLT HVAC Drive Selection VLT HVAC Drive Design Guide 50 MG 11 B9 02 VLT is a registered Danfoss trademark 3...
Страница 78: ...5 How to Install VLT HVAC Drive Design Guide 78 MG 11 B9 02 VLT is a registered Danfoss trademark 5...
Страница 118: ...6 Application Examples VLT HVAC Drive Design Guide 118 MG 11 B9 02 VLT is a registered Danfoss trademark 6...
Страница 128: ...7 RS 485 Installation and Set up VLT HVAC Drive Design Guide 128 MG 11 B9 02 VLT is a registered Danfoss trademark 7...