3.5.4 3-5* Ramp 2
Choosing ramp parameters, see 3-4*.
3-51 Ramp 2 Ramp-up Time
Range:
Function:
10.00 s*
[1.00 - 3600.00 s]
Enter the ramp-up time, i.e., the acceleration time from 0 RPM to par.1-25
.
Choose a ramp-up time such that the output current does not exceed the current limit in par.
4-18
during ramping. See ramp-down time in par.3-52
.
par
. 3
−
51 =
tacc
×
nnorm
par
. 1
−
25
ref
rpm
s
3-52 Ramp 2 Ramp-down Time
Range:
Function:
20.00 s*
[1.00 - 3600.00 s]
Enter the ramp-down time, i.e., the deceleration time from par.1-25
Choose a ramp-down time such that no overvoltage arises in the inverter due to regenerative op-
eration of the motor, and such that the generated current does not exceed the current limit set in
par.4-18
. See ramp-up time in par.3-51
.
par
.3
−
52 =
tdec
×
nnorm
par
. 1
−
25
ref
rpm
s
3.5.5 3-8* Other Ramps
Configure parameters for special ramps such as jog or quick stop, for example.
3-80 Jog Ramp Time
Range:
Function:
20.00 s*
[1.00 - 3600.00 s]
Enter the jog ramp time, i.e., the acceleration/deceleration time between 0 RPM and the rated motor
speed (n
M,N
) (set in par.1-25
). Ensure that the resultant output current re-
quired for the given jog ramp time does not exceed the current limit in par.4-18
jog ramp time starts upon activation of a jog signal via the control panel, a selected digital input,
or the serial communication port.
par
. 3
−
80 =
tjog
×
nnorm
par
. 1
−
25
jog
speed
par
. 3
−
19
s
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-38
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3