3.5.2 3-1* References
Parameters for setting up the reference sources.
Select the preset reference(s).
Select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in parameter group 5.1*.
3-10 Preset Reference
Array [8]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter up to eight different preset references (0–7) in this parameter, using array programming. The
preset reference is stated as a percentage of the value Ref
MAX
, for
closed-loop see par.20-14
). When using preset references, select Pre-
set ref. bit 0 / 1 / 2 [16], [17] or [18] for the corresponding digital inputs in parameter group 5-1*
Digital Inputs.
3-11 Jog Speed [Hz]
Range:
Function:
10.0 Hz*
[0.0 - par. 4-14 Hz]
The jog speed is a fixed output speed at which the adjustable frequency drive is running when the
jog function is activated.
See also par.3-80
.
3-13 Reference Site
Option:
Function:
Select which reference site to activate.
[0] *
Linked to Hand / Auto
Use local reference when in hand mode; or remote reference when in auto mode.
[1]
Remote
Use remote reference in both hand mode and auto mode.
[2]
Local
Use local reference in both hand mode and auto mode.
NOTE!
When set to Local [2], the adjustable frequency drive will start with this setting
again following a 'power-down'.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-34
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3