26-37 Term. X42/5 Live Zero
Option:
Function:
This parameter makes it possible to enable the live zero monitoring, for example where the analog
input is a part of the adjustable frequency drive control, rather than being used as part of a decentral
I/O system, such as a building management system.
[0]
Disabled
[1] *
Enabled
26-40 Terminal X42/7 Output
Option:
Function:
Set the function of terminal X42/7 as an analog voltage output.
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed-loop 1
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
[139]
Bus ctrl.
[141]
Bus ctrl t.o.
26-41 Terminal X42/7 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale the minimum output of the selected analog signal at terminal X42/7, as a percentage of the
maximum signal level, for example if a 0 V (or 0 Hz) is desired at 25% of the maximum output
value. Then program 25%. Scaling values up to 100% can never be higher than the corresponding
setting in par.26-42
See principle graph for par.6-51
26-42 Terminal X42/7 Max. Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale the maximum output of the selected analog signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10 V is the desired
output current at a value between 0–100% of the full-scale output, program the percentage value
in the parameter, i.e., 50% = 10 V. If a voltage between 0 and 10V is desired at maximum output,
calculate the percentage as follows:
(
10
V
desired
maximum
voltage
)
x
100 %
i.e.
5
V
: 10
V
5
V
× 100 % = 200 %
See principle graph for par.6-52