24-03 Fire Mode Min Reference
Range:
Function:
0 FireMo-
deUnit*
[-999999.999 - par. 24-04 FireMo-
deUnit]
Minimum value for the reference/setpoint (limiting the sum of value in par.24-05
and value of signal on input selected in par.24-06
If running in open-loop when fire mode is active, the unit is chosen by the setting of par.0-02
. For closed-loop, the unit is selected in par.24-02
24-04 Fire Mode Max Reference
Range:
Function:
50.000 Fire-
ModeUnit*
[par. 24-03 - 999999.999 FireMo-
deUnit]
Maximum value for the reference/setpoint (limiting the sum of value in par.24-05
and value of signal on input selected in par.24-06
If running in open-loop when fire mode is active, the unit is chosen by the setting of par.0-02
. For closed-loop, the unit is selected in par.24-02
24-05 Fire Mode Preset Reference
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter the required preset reference/setpoint as a percentage of the Fire Mode Max Reference set
in par.24-04
. The set value will be added to the value represented by the
signal on the analog input selected in
par.24-06 Fire Mode Reference Source, Fire Mode Reference
Source
.
VLT
®