5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 29 when it is configured as [Bus
Controlled Timeout] and timeout is detected
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 27 when it is configured as [Bus
Controlled.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Contains the frequency to apply to the digital output terminal 6 when it is configured as [Bus Con-
trolled Timeout] and timeout is detected.
3.8 Main Menu - Analog In/Out - Group 6
3.8.1 6-** Analog In/Out
Parameter group for configuring the analog input and output.
3.8.2 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The adjustable frequency drive is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be allocated to either voltage (0–10
V) or current input (0/4–20 mA)
NOTE!
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Timeout time period. Live Zero Timeout Time is active for analog inputs, (i.e.,
terminal 53 or terminal 54), allocated to current and used as reference or feedback sources. If the
reference signal value associated with the selected current input falls below 50% of the value set
in par.6-10
, par.6-12
, par.6-20
or par.6-22
for a time period longer than the time set in par.
, the function selected in par.6-01
will be
activated.