4-53 Warning Speed High
Range:
Function:
Size
related
*
[ par.
4-52 -
60000
RPM]
NOTICE
Any changes in
reset the value
in
parameter 4-53 Warning Speed High
to the same value as set in
parameter 4-13 Motor Speed High Limit
[RPM]
.
If a different value is needed in
parameter 4-53 Warning Speed High
, it
must be set after programming of
parameter 4-13 Motor Speed High Limit
[RPM]
.
Enter the n
HIGH
value. When the motor speed
exceeds this limit (n
HIGH
), the display reads
Speed high
. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29, and on relay output 01 or
02. Programme the upper signal limit of the
motor speed, n
HIGH
, within the normal
working range of the frequency converter.
Refer to
4-54 Warning Reference Low
Range:
Function:
-999999.999
*
[ -999999.999 -
par. 4-55 ]
Enter the lower reference limit.
When the actual reference drops
below this limit, the display
indicates Ref
Low
. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29, and on relay
output 01 or 02.
4-55 Warning Reference High
Range:
Function:
999999.999
*
[ par. 4-54 -
999999.999 ]
Enter the upper reference limit.
When the actual reference exceeds
this limit, the display reads
Ref
High
.
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29, and
on relay output 01 or 02.
4-56 Warning Feedback Low
Range:
Function:
-999999.999
ProcessCtrlUnit
*
[ -999999.999 -
par. 4-57
ProcessCtrlUnit]
Enter the lower feedback
limit. When the feedback
drops below this limit, the
display reads
Feedb
Low
. The
signal outputs can be
programmed to produce a
status signal on terminal
4-56 Warning Feedback Low
Range:
Function:
27 or 29, and on relay
output 01 or 02.
4-57 Warning Feedback High
Range:
Function:
999999.999
ProcessCtrlUnit
*
[ par. 4-56 -
999999.999
ProcessCtrlUnit]
Enter the upper feedback
limit. When the feedback
exceeds this limit, the
display reads
Feedb
High
.
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29, and on relay
output 01 or 02.
4-58 Missing Motor Phase Function
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Displays an alarm if motor phase is
missing.
[0] Disabled
No alarm is displayed if a missing motor
phase occurs.
[1] Trip 100 ms
An alarm is displayed if a missing motor
phase occurs.
[2] Trip 1000 ms
[3] Trip 100ms 3ph
detec.
[5] Motor Check
3.6.3 4-6* Speed Bypass
Some systems require that certain output frequencies or
speeds are avoided, due to resonance problems in the
system. A maximum of 4 frequency or speed ranges can
be avoided.
4-60 Bypass Speed From [RPM]
Array [4]
Range:
Function:
Size related
*
[ 0 - par.
4-13 RPM]
Some systems require that certain
output frequencies or speeds are
avoided due to resonance problems
in the system. Enter the lower limits
of the speeds to be avoided.
Parameter Descriptions
Programming Guide
MG11CE02