26-52 Terminal X42/9 Max. Scale
See
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10
V at full scale; or 10 V at an output below 100%
of the maximum signal value. If 10 V is the
desired output current at a value between
0-100% of the full-scale output, programme the
percentage value in the parameter, that is,
50%=10 V. If a voltage between 0 and 10 V is
desired at maximum output, calculate the
percentage as follows:
that is
5V : 10V
5V × 100 % = 200 %
26-53 Terminal X42/9 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/9 if
controlled by bus.
26-54 Terminal X42/9 Timeout Preset
Range:
Function:
0 %
*
[0 - 100
%]
Holds the preset level of terminal X42/9.
If a bus time-out and a time-out function are
selected in
parameter 26-60 Terminal X42/11
, the output presets to this level.
3.24.7 26-6* Analog Out X42/11
Parameters for configuring the scaling and output function
for analog output, terminal X42/11.
26-60 Terminal X42/11 Output
Option:
Function:
Set the function of terminal X42/11.
[0]
*
No operation
[100] Output freq.
0-100
0–100 Hz, (0–10 V).
[101] Reference Min-
Max
Minimum reference - maximum
reference, (0–10 V).
[102] Feedback
+-200%
-200% to +200% of
3-03 Maximum
Reference
, (0–10 V).
[103] Motor cur. 0-
Imax
0–inverter maximum current
(
parameter 16-37 Inv. Max. Current
), (0–10
V).
[104] Torque 0-Tlim
0–torque limit (
), (0–10 V).
[105] Torque 0-Tnom
0–motor rated torque, (0–0 V).
[106] Power 0-Pnom
0–motor rated power, (0–10 V).
26-60 Terminal X42/11 Output
Option:
Function:
[107] Speed 0-
HighLim
0–speed high limit
(
parameter 4-13 Motor Speed High Limit
and
), (0–10 V).
[113] Ext. Closed Loop
1
0–100%, (0–10 V).
[114] Ext. Closed Loop
2
0–100%, (0–10 V).
[115] Ext. Closed Loop
3
0–100%, (0–10 V).
[139] Bus ctrl.
0–100%, (0–10 V).
[141] Bus ctrl t.o.
0–100%, (0–10 V).
26-61 Terminal X42/11 Min. Scale
For more information, see
chapter 3.8.7 6-51 Terminal 42 Output
Range:
Function:
0 %
*
[0 - 200
%]
Scale the minimum output of the selected
analog signal at terminal X42/11, as a
percentage of the maximum signal level. For
example, if 0 V is desired at 25% of the
maximum output value, programme 25%.
Scaling values up to 100% can never be higher
than the corresponding setting in
parameter 26-62 Terminal X42/11 Max. Scale
.
26-62 Terminal X42/11 Max. Scale
See
.
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10
V at full scale; or 10 V at an output below 100%
of the maximum signal value. For example, If 10
V is the desired output current at a value
between 0-100% of the full-scale output,
programme the percentage value in the
parameter, that is, 50%=10 V. If a voltage
between 0 and 10 V is desired at maximum
output, calculate the percentage as follows:
10V
desired maximum voltage x100 %
that is
5V : 10V
5V x100 % = 200 %
26-63 Terminal X42/11 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/11 if
controlled by bus.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
206
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02
3
3