26-10 Terminal X42/1 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-31 V]
Enter the low-voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter 26-14 Term. X42/1 Low Ref./Feedb.
Value
26-11 Terminal X42/1 High Voltage
Range:
Function:
10 V
*
[ par. 6-30
- 10 V]
Enter the high-voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 26-15 Term. X42/1 High Ref./Feedb.
Value
.
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value that
corresponds to the low-voltage value set
in
parameter 26-10 Terminal X42/1 Low
.
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value
that corresponds to the high-voltage
value set in
.
26-16 Term. X42/1 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
This is a first-order digital low-pass filter
time constant for suppressing noise in
terminal X42/1. A high time constant
value improves dampening, but also
increases the time delay through the
filter.
26-17 Term. X42/1 Live Zero
Option:
Function:
This parameter makes it possible to enable the
live zero monitoring, example, where the analog
input is the frequency converter control, rather
than being used as a decentral I/O system, such
as a building management system.
[0]
Disabled
[1]
*
Enabled
3.24.3 26-2* Analog Input X42/3
Parameters for configuring the scaling and limits for analog
input, terminal X42/3.
26-20 Terminal X42/3 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-31 V]
Enter the low-voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter 26-24 Term. X42/3 Low Ref./Feedb.
Value
.
26-21 Terminal X42/3 High Voltage
Range:
Function:
10 V
*
[ par. 6-30
- 10 V]
Enter the high-voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 26-25 Term. X42/3 High Ref./Feedb.
Value
.
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value that
corresponds to the low-voltage value set
in
parameter 26-20 Terminal X42/3 Low
26-25 Term. X42/3 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value
that corresponds to the high-voltage
value set in
.
26-26 Term. X42/3 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the time constant. This is a first-
order digital low-pass filter time constant
for suppressing noise in terminal X42/3. A
high time constant value improves
dampening, but also increases the time
delay through the filter.
26-27 Term. X42/3 Live Zero
Option:
Function:
This parameter makes it possible to enable the
live zero monitoring, example, where the analog
input is the frequency converter control, rather
than being used as a decentral I/O system, such
as a building management system.
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
203
3
3