25-50 Lead Pump Alternation
Option:
Function:
[0]
*
Off
No alternation of lead pump function takes
place. It is not possible to set this parameter to
options other that
[0] Off
if
is set other than
[0]
Direct on Line
.
[1] At staging
Alternation of the lead pump function takes
place when staging another pump.
[2] At
command
Alternation of the lead pump function takes
place at an external command signal or a pre-
programmed event. See
parameter 25-51 Alternation Event
for available
options.
[3] At staging
or
command
Alternation of the variable speed (lead) pump
takes place at staging or the At command
signal (see above).
25-51 Alternation Event
Option:
Function:
This parameter is only active if the options
[2]
At Command
or
[3] At Staging or Command
have been selected in
. If an alternation event is
selected, the alternation of lead pump takes
place every time the event occurs.
[0]
*
External
Alternation takes place when a signal is
applied to 1 of the digital inputs on the
terminal strip and this input has been assigned
to
[121] Lead Pump Alternation
in
parameter
group 5-1*, Digital Inputs
.
[1] Alternation
Time
Interval
Alternation takes place every time
parameter 25-52 Alternation Time Interval
expires.
[2] Sleep Mode Alternation takes place each time the lead
pump goes into sleep mode. Set
to
[1] Sleep Mode
or
apply an external signal must be applied for
this function.
[3] Predefined
Time
Alternation takes place at a defined time of the
day. If
parameter 25-54 Alternation Predefined
is set, the alternation is carried out every
day at the specified time. Default time is
midnight (00:00 or 12:00AM depending on the
time format).
25-52 Alternation Time Interval
Range:
Function:
24
h
*
[1 -
999 h]
If selecting
[1] Alternation Time Interval
in
parameter 25-51 Alternation Event
, the alternation
of the variable speed pump takes place every
time the alternation time interval expires (can be
checked in
parameter 25-53 Alternation Timer
25-53 Alternation Timer Value
Range:
Function:
0
*
[0 - 7 ] Readout parameter for the alternation time interval
value set in
parameter 25-52 Alternation Time
25-54 Alternation Predefined Time
Range:
Function:
Size
related
*
[ 0 -
0 ]
If selecting
[3] Predefined Time
in
parameter 25-51 Alternation Event
the variable
speed pump alternation is carried out every
day at the specified time set in alternation
predefined time. Default time is midnight
(00:00 or 12:00AM depending on the time
format).
25-55 Alternate if Load < 50%
Option:
Function:
NOTICE
Only valid if
is different from
[0] Off
.
If selecting
[1] Enabled
, the pump alternation can
only occur if the capacity is equal to or below
50%. The capacity calculation is the ratio of
running pumps (including the variable speed
pump) to the total number of available pumps
(including variable speed pump, but not those
that are interlocked).
Capacity =
N
RUNNING
N
TOTAL
× 100 %
For the basic cascade controller, all pumps are
equal size.
[0]
Disabled The lead pump alternation takes place at any
pump capacity.
[1]
*
Enabled The lead pump function is alternated only if the
number of pumps running are providing less
than 50% of total pump capacity.
Parameter Descriptions
Programming Guide
MG11CE02