Counter 00 always contains the oldest data. A counter
covers a period from XX:00 to XX:59 if hours or 00:00 to
23:59 if days.
If logging either the last hours or last days, the counters
shift contents at XX:00 every hour or at 00:00 every day.
The counter with highest index is always subject to update
(containing data for the actual hour since XX:00 or the
actual day since 00:00).
The contents of counters can be displayed as bars on the
LCP. Select
Quick Menu
,
Loggings
,
Energy Log: Trending
Continued Bin/Trending Timed Bin/Trending Comparison
.
23-50 Energy Log Resolution
Option:
Function:
NOTICE
The frequency converter has no back-
up of the clock function and the set
date/time resets to default (2000-01-01
00:00) after a power-down unless a real
time clock-module with back-up is
installed. Consequently, the logging is
stopped until date/time is readjusted
in
. In
it is possible
to programme a warning if the clock
not has been set properly, for example
after a power-down.
Select the desired type of period for logging
of consumption.
[0] Hour of Day
,
[1] Day of
Week
, or
[2] Day of Month
. The counters
contain the logging data from the
programmed date/time for start
(
) and the
numbers of hours/days as programmed for
(
parameter 23-50 Energy Log Resolution
The logging starts on the date programmed
in
, and continues
until 1 day/week/month has passed.
[5] Last
24 Hours
,
[6] Last 7 Days
or
[7] Last 5 Weeks
.
The counters contain data for 1 day, 1 week
or 5 weeks back in time, and up to the actual
time.
The logging starts at the date programmed
in
. In all cases,
the period split refers to operating hours
(time where frequency converter is powered
up).
[0]
Hour of Day
[1]
Day of Week
[2]
Day of
Month
[5]
*
Last 24
Hours
[6]
Last 7 Days
23-50 Energy Log Resolution
Option:
Function:
[7]
Last 5
Weeks
23-51 Period Start
Range:
Function:
Size
related
*
[ 0 -
0 ]
NOTICE
When mounting an analog I/O MCB 109
option card, a battery back-up of the
date and time is included.
Set the date and time at which the energy log
starts updating the counters. First, data are
stored in counter [00] and start at the time/
date programmed in this parameter.
Date format depends on setting in
and time format
on setting in
.
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.