3.14 Parameters: 14-** Main Menu - Special
Functions
3.14.1 14-0* Inverter Switching
14-00 Switching Pattern
Option:
Function:
Select the switching pattern: 60° AVM or SFAVM.
[0] 60 AVM
[1] SFAVM
14-01 Switching Frequency
Option:
Function:
Select the inverter switching frequency. Changing
the switching frequency can help reduce acoustic
noise from the motor.
NOTICE
The output frequency value of the
frequency converter must never exceed
1/10 of the switching frequency. When the
motor is running, adjust the switching
frequency in
until the motor is as noiseless as
possible. See also
parameter 14-00 Switching Pattern
. For
information about derating, see the
relevant design guide.
[0]
1.0 kHz
[1]
1.5 kHz
[2]
2.0 kHz
[3]
2.5 kHz
[4]
3.0 kHz
[5]
3.5 kHz
[6]
4.0 kHz
[7]
5.0 kHz
[8]
6.0 kHz
[9]
7.0 kHz
[10] 8.0 kHz
[11] 10.0 kHz
[12] 12.0kHz
[13] 14.0 kHz
[14] 16.0kHz
14-03 Overmodulation
Option: Function:
[0]
*
Off Selects no overmodulation of the output voltage to
avoid torque ripple on the motor shaft.
[1]
On The overmodulation function generates an extra
voltage of up to 8% of U
max
output voltage without
overmodulation. This extra voltage results in an extra
torque of 10-12% in the middle of the oversyncronous
range (from 0% at nominal speed rising to approxi-
mately 12% at double nominal speed).
14-04 PWM Random
Option: Function:
[0]
*
Off No change of the acoustic motor switching noise.
[1]
On Transforms the acoustic motor switching noise from a
clear ringing tone to a less noticeable white noise. This
is achieved by slightly and randomly altering the
synchronism of the pulse width modulated output
phases.
3.14.2 14-1* Mains On/Off
Parameters for configuring mains failure monitoring and
handling.
14-10 Mains Failure
Option:
Function:
Select the function at which the frequency
converter must act, when the threshold set in
parameter 14-11 Mains Voltage at Mains Fault
has
been reached or a
Mains Failure Inverse
command is activated via one of the digital
inputs (parameter group 5-1* Digital Inputs).
Only selection
[0] No function
,
[3] Coasting
or
[6]
Alarm
is available when
is set to
[1] PM non-salient SPM
[0]
*
No
function
The energy left in the capacitor bank is used to
drive the motor, but is discharged.
[1]
Ctrl.
ramp-
down
The frequency converter performs a controlled
ramp down.
must
be set to
[0] Off
.
[3]
Coasting
The inverter turns off and the capacitor bank
backs up the control card. Backing up control
card ensures a faster restart when mains
reconnected (at short power zags).
[4]
Kinetic
back-up
The frequency converter rides through by
controlling speed for generative operation of the
motor utilising the moment of inertia of the
system as long as sufficient energy is present.
[6]
Alarm
DC Voltage
Output Speed rpm
Over Voltage Control Level
Mains
Time
130B
T101.10
Par 14-11
Illustration 3.37 Controlled Ramp Down - Short Mains Failure.