
Voltage [V]
Minimum waiting time (minutes)
4
7
15
20
30
40
200–240
1.1–3.7 kW
(1.50–5 hp)
–
5.5–45 kW
(7.5–60 hp)
–
–
–
380–480
1.1–7.5 kW
(1.50–10 hp)
–
11–90 kW
(15–121 hp)
–
–
315–1000 kW
(450–1350 hp)
400
–
–
–
90–315 kW
(121–450 hp)
–
–
500
–
–
–
110–355 kW
(150–500 hp)
–
–
525
–
–
–
75–315 kW
(100–450 hp)
–
–
525–600
1.1–7.5 kW
(1.50–10 hp)
–
11–90 kW
(15–121 hp)
–
–
–
690
–
–
–
90–315 kW
(100– 350 hp)
–
–
525–690
–
1.1–7.5 kW
(1.50–10 hp)
11–90 kW
(15–121 hp)
–
400–1400 kW
(500–1550 hp)
450–1400 kW
(600–1550 hp)
–
Table 1.1 Discharge Time, VLT
®
HVAC Drive FC 102
Voltage [V]
Minimum waiting time (minutes)
4
7
15
20
40
200–240
0.25–3.7 kW
(0.34–5 hp)
–
5.5–37 kW
(7.5–50 hp)
–
–
380–480
0.25–7.5 kW
(0.34–10 hp)
–
11–75 kW
(15–100 hp)
110–315
(150–450 hp)
355–450
(500–600 hp)
355–560
(500–750 hp)
525–600
0.75–7.5 kW
(1.0–10 hp)
–
11–75 kW
(15–100 hp)
–
–
525–690
–
1.5–7.5 kW
(2–10 hp)
11–75 kW
(15–100 hp)
55–400
(75–400 hp)
450–630
(600–750 hp)
450–800
(600–950 hp)
Table 1.2 Discharge Time, VLT
®
Refrigeration Drive FC 103
Voltage [V]
Minimum waiting time (minutes)
4
7
15
20
30
40
200–240
0.25–3.7 kW
(0.34–5 hp)
–
5.5–45 kW
(7.5–60 hp)
–
–
–
380–480
0.37–7.5 kW
(0.5–10 hp)
–
11–90 kW
(15–121 hp)
110–315 kW
(150–450 hp)
–
315–1000 kW
(450–1350 hp)
355–560 kW
(500–750 hp)
525–600
0.75–7.5 kW
(1–10 hp)
–
11–90 kW
(15–121 hp)
–
400–1400 kW
(400–1550 hp)
–
525–690
–
1.1–7.5 kW
(1.5–10 hp)
11–90 kW
(10–100 hp)
75–400 kW
(75–400 hp)
–
450–800 kW
(450–950 hp)
Table 1.3 Discharge Time, VLT
®
AQUA Drive FC 202
Installation Instructions
Control Card VLT
®
FC Series
2
Danfoss A/S © 03/2017 All rights reserved.
MI93A102