3.12 Main Menu - Data Readouts - Group 16
3.12.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the
adjustable frequency drive via the serial
communication port in hex code.
Bit number
15 14
13
12
11
10
9 8 7 6 5 4 3 2 1 0
Bit Bit = 0
Bit = 1
00 Preset reference choice lsb
01 Preset reference choice second bit of
preset references
02 DC brake
Ramp
03 Coasting
Enable
04 Quick stop
Ramp
05 Freeze output
Ramp
06 Ramp stop
Start
07 No function
Reset
08 No function
Jog
09 Ramp 1
Ramp 2
10 Data not valid
Valid
11 Relay_A not active
Relay_A activated
12 Relay_B not active
Relay_B activated
13 Choice of Set-up lsb
14 No function
No function
15 No function
Reversing
Table 3.8 Control Word
16-01 Reference [Unit]
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-4999 - 4999
ReferenceFeed-
backUnit]
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in
(Hz).
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 - 200 %]
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the adjustable
frequency drive via the serial communication
port in hex code.
Bit number
15
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
Bit = 0
Bit = 1
00
Control not ready
Ready
01
VLT not ready
Ready
02
Coasting
Enable
03
No fault
Trip
04
No warning
Warning
05
Reserved
06
No trip lock
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Bus control
10
Out of speed range
Frequency OK
11
Not running
Running
12
No function
No function
13
Voltage OK
Above limit
14
Current OK
Above limit
15
Temperature OK
Above limit
Table 3.9 Status Word
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-200 - 200 %]
16-09 Custom Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[0 - 9999
CustomRea-
doutUnit]
View the user-defined
readouts as defined in
and
. Custom
Readout
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 - 1000 kW] Displays DC link power in kW. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-54
MG18B222 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...