13-10 Comparator Operand
Array [6]
Option:
Function:
[7]
Motor voltage
[12] Analog input AI53
[13] Analog input AI54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
Array [6]
Option:
Function:
[0] Less Than (<)
Select
[0] <
for the result of the evaluation
to be TRUE, when the variable selected in
is smaller than
the fixed value in
.
The result will be FALSE, if the variable
selected in
is
greater than the fixed value in
.
[1] Approx.Equal (~) Select
[1] ≈
for the result of the evaluation
to be TRUE, when the variable selected in
is approximately
equal to the fixed value in
.
[2] Greater Than (>) Select
[2] >
for the inverse logic of option
[0] <
.
13-12 Comparator Value
Array [6]
Range:
Function:
0
*
[-9999 -
9999 ]
Enter the ‘trigger level’ for the variable that
is monitored by this comparator. This is an
array parameter containing comparator
values 0 to 5.
3.9.4 13-2*Timers
Use the result (TRUE or FALSE) from
timers
directly to
define an
event
(see
), or as
Boolean input in a
logic rule
(see
or
).
A timer is only FALSE when started by an action (i.e.,
[29]
Start timer 1
) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [8]
Range:
Function:
0 s
*
[0 - 3600
s]
Enter the value to define the duration of the
FALSE output from the programmed timer. A
timer is only FALSE if it is started by an action
(see
13-52 SL Controller Action
[29-31] and
13-52 SL Controller Action
[70-74] Start timer X)
and until the timer value has elapsed. Array
par. containing timers 0 to 7.
3.9.5 13-4* Logic Rules
Combine up to three Boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select Boolean inputs for the calculation in
and
. Define the operators used to logically combine
the selected inputs in
and
.
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Figure 3.15
Priority of calculation
The results of
and
are calculated
first. The outcome (TRUE / FALSE) of this calculation is
combined with the settings of
and
, yielding the final result
(TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the logic
rule.
[2]
Running
See
for further
description.
[3]
In range
See
for further
description.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-43
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...