5.1.4 2-** Brakes
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
2-0* DC-Brake
2-00
DC Hold/Motor Preheat Current
50 %
All set-ups
TRUE
0
Uint16
2-01
DC Brake Current
50 %
All set-ups
TRUE
0
Uint16
2-02
DC Braking Time
10 s
All set-ups
TRUE
-1
Uint16
2-04
DC Brake Cut In Speed
0 Hz
All set-ups
TRUE
-1
Uint16
2-06
Parking Current
100 %
All set-ups
TRUE
0
Uint16
2-07
Parking Time
3 s
All set-ups
TRUE
-1
Uint16
2-1* Brake Energy Funct.
2-10
Brake Function
[0] Off
All set-ups
TRUE
-
Uint8
2-16
AC Brake, Max current
100 %
All set-ups
TRUE
-1
Uint16
2-17
Over-voltage Control
[2] Enabled
All set-ups
TRUE
-
Uint8
5.1.5 3-** Reference/Ramps
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion
index
Type
3-0* Reference Limits
3-02
Minimum Reference
0 ReferenceFeedbackUnit
All set-ups
TRUE
-3
Int32
3-03
Maximum Reference
ExpressionLimit
All set-ups
TRUE
-3
Int32
3-1* References
3-10
Preset Reference
0 %
All set-ups
TRUE
-2
Int16
3-11
Jog Speed [Hz]
5 Hz
All set-ups
TRUE
-1
Uint16
3-14
Preset Relative Reference
0 %
All set-ups
TRUE
-2
Int16
3-15
Reference 1 Source
[1] Analog in 53
All set-ups
TRUE
-
Uint8
3-16
Reference 2 Source
[2] Analog in 54
All set-ups
TRUE
-
Uint8
3-17
Reference 3 Source
[11] Local bus reference
All set-ups
TRUE
-
Uint8
3-4* Ramp 1
3-41
Ramp 1 Ramp Up Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
3-42
Ramp 1 Ramp Down Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
3-5* Ramp 2
3-51
Ramp 2 Ramp Up Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
3-52
Ramp 2 Ramp Down Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
3-8* Other Ramps
3-80
Jog Ramp Time
ExpressionLimit
All set-ups
TRUE
-2
Uint32
3-81
Quick Stop Ramp Time
ExpressionLimit
1 set-up
TRUE
-2
Uint32
5.1.6 4-** Limits/Warnings
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion
index
Type
4-1* Motor Limits
4-10
Motor Speed Direction
[2] Both directions
All set-ups
FALSE
-
Uint8
4-12
Motor Speed Low Limit [Hz]
0 Hz
All set-ups
FALSE
-1
Uint16
4-14
Motor Speed High Limit [Hz]
65 Hz
All set-ups
FALSE
-1
Uint16
4-18
Current Limit
110 %
All set-ups
TRUE
0
Uint16
4-19
Max Output Frequency
ExpressionLimit
All set-ups
FALSE
-1
Uint16
4-4* Adj. Warnings 2