13-02 Stop Event
Option:
Function:
[34]
Digital input DI19
[35]
Digital input DI27 Use the value of DI27 in the logic rule
(High = TRUE).
[36]
Digital input DI29 Use the value of DI29 in the logic rule
(High = TRUE).
[39]
Start command
This event is TRUE if the frequency
converter is started by any means
(either via digital input, fieldbus or
other).
[40]
*
Drive stopped
This event is TRUE if the frequency
converter is stopped or coasted by
any means (either via digital input,
fieldbus or other).
[42]
Auto Reset Trip
This event is TRUE if the frequency
converter is tripped (but not trip-
locked) and an Automatic Reset is
issued.
[50]
Comparator 4
Use the result of comparator 4 in the
logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the
logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic
rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic
rule.
[83]
Broken Belt
A broken belt condition has been
detected. This function must be
enabled in
.
13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset
SLC
Retains programmed settings in all group 13
parameters (
13-** Smart Logic
).
[1]
Reset SLC
Resets all group 13 parameters (
13-** Smart
Logic
) to default settings.
3.9.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 3.14 Comparators
In addition, there are digital values that are compared to
fixed time values. See explanation in
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option:
Function:
Select the variable to be monitored by
the comparator.
[0]
*
Disabled
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor Current
[6]
Motor power
[7]
Motor voltage
[12] Analog input AI53
[13] Analog input AI54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
Array [6]
Option:
Function:
[0]
Less Than (<)
Select
[0] <
for the result of the evaluation
to be TRUE, when the variable selected in
is smaller than
the fixed value in
The result is FALSE, if the variable selected
in
is greater
than the fixed value in
.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
59