background image

VLT

® 

MCA 121 EtherNet/IP Add On Instruction 

MI3xxxxxxx - VLT

®

is a registered Danfoss trademark 

3

 

 

 
 
 
 
2.0 General Configuration of the FC Drive

 

 

The following procedure goes over the various parameters required to get the FC drive communicating over EtherNet/IP. 

 

1. 

When the FC drive is first commissioned the following parameters should be set before any other changes are 

made to the drive via the Main Menu. 

 

Parameter

 

Description

 

Setting

 

0-03 Regional 

Settings 

[0] 

International 

 

 

2. 

To enter the motor data into the drive, a quick setup should be performed.  This function of the drive is accessed 

from the Quick Menu by pressing the 

Quick Menu

 button on the display and selecting 

Q2  Quick Setup

. This can 

be performed now or at a later time, but must be done prior to running the motor to ensure proper operation. 

 

3. 

Verify the setting of the following parameters to ensure that the PLC will have control of the drive. 

 

Parameter

 

Description

 

Setting

 

8-01 

Control Site 

[0] Digital and ctrl.word, or 
[2] Control word only 

8-02 

Control Word Source 

[3] Option A 

 

 

A connection between terminal 12/13 and terminal 27 is required, if parameter 8-01 is set to [0] “Digital and ctrl. 
word”. 

 

 

4. 

The default setting of the drive allows the drive to continue operation if the communication is lost to the 

PLC.  If this operation is not desired change the following parameter via the Main Menu. 

 

Parameter

 

Description

 

Setting

 

8-04 

Control Word Timeout Function 

[0] Off, or
[1] Freeze Output, or 
[2] Stop, or 
[3] Jogging, or 
[4] Max Speed, or 
[5] Stop and trip 

 

 

5. 

AOI requires the profile of the control word to be set to FC Profile. If the Control Word Profile is set to ODVA, it will lead 

to malfunction of the AOI. Verify that following parameter is set correctly via the Main Menu.  See the EtherNet/IP manual 
MG.90.Jx.yy for more information. 

 

Parameter

 

Description

 

Setting

 

8-10 

Control Word Profile 

[0] FC Profile. 

 

6. Next the IP settings of the drive need to be configured.  To do this set the following parameters via the Main menu.  If 

the IP settings are being set via a DIP switches, BOOTP or DHCP Server see the EtherNet/IP manual MG.90.Jx.yy for 
more information. 

 

Parameter

 

Description

 

Setting

 

12-00 

IP Address Assignment 

[0] Manual 

12-01 IP 

Address 

e.g. 

192.168.1.10 

12-02 Subnet 

Mask 

e.g. 

255.255.255.000 

 
 

 

Содержание VLT FC Series

Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction VLT FC Series Add On Instruction for MCA 121 EtherNet IP...

Страница 2: ...the end user For an example program open the provided sample program EthIP acd Note that when using this version of the AOI version 20 0 or later of RSLogix 5000 Earlier versions of RSLogix do not su...

Страница 3: ...ource 3 Option A A connection between terminal 12 13 and terminal 27 is required if parameter 8 01 is set to 0 Digital and ctrl word 4 The default setting of the drive allows the drive to continue ope...

Страница 4: ...the following parameters via the Main Menu Parameter Description Setting 12 21 0 Process Data Config Write 1680 Fieldbus CTW 1 12 21 1 1682 Fieldbus REF 1 12 22 0 Process Data Config Read 1603 Status...

Страница 5: ...2 Import the Add On Instruction by selecting Add On Instruction in the navigation tree and press the right mouse button and select Import Add On Instruction Figure 1 Import Add On Instruction 3 Select...

Страница 6: ...in the Import content windows If warnings and or errors exist the Add On Instruction will not work properly If no Errors Warnings are present then the Add On Instruction can be imported by pressing t...

Страница 7: ...e following module dialog will appear as in figure 5 1 Insert the IP address used in Par 12 01 e g 192 168 1 10 All IP addresses must unique for each device connected to the network 2 Set the Name fie...

Страница 8: ...Add On Instruction 5 0 Setting up the Add On Instruction The Danfoss Add On Instruction can be copied to the PLC s rung This is done by opening the Add On Instruction folder and drag and drop the VLT...

Страница 9: ...tions Reset Boolean In transition from 0 to 1 a fault trip can be reset MRV Real Main Reference Value Speed set point in of nominal motor speed The function of the output tags are Name Type Descriptio...

Страница 10: ...the actual drive e g FC302 I1 Data New tags can be created by right clicking in the desired field and selecting New tag The same procedure must be done with the DriveOut field in order to control the...

Страница 11: ...www danfoss com drives 130R0xyz MIyyuxxxx Rev 2013 09 20...

Отзывы: