manualshive.com logo in svg
background image

Drive Rating

FC 102/FC 202

FC 302

[HP]

[kW]

208-230 V

460-480 V

575-600 V

208-230 V

460-480 V

575-600 V

30

22

JJN-125 125 A,

300 V, Class T

JJS-60 60 A, 600 V,

Class T

JJS-50 50 A, 600 V,

Class T

FWX-150A 150 A,

250 V

JJS-80 80 A, 600 V,

Class T

JJS-60 60 A, 600 V,

Class T

40

30

FWX-150A 150 A,

250 V

JJS-80 80 A, 600 V,

Class T

JJS-60 60 A, 600 V,

Class T

FWX-200A 200 A,

250 V

JJS-100 100 A,

600 V, Class T

JJS-80 80 A, 600 V,

Class T

50

37

FWX-200A 200 A,

250 V

JJS-100 100 A,

600 V, Class T

JJS-80 80 A, 600 V,

Class T

FWX-250A 250 A,

250 V

JJS-125 125 A,

600 V, Class T

JJS-100 100 A,

600 V, Class T

60

45

FWX-250A 250 A,

250 V

JJS-125 125 A,

600 V, Class T

JJS-100 100 A,

600 V, Class T

n/a

JJS-150 150 A,

600 V, Class T

JJS-125 125 A,

600 V, Class T

75

55

n/a

JJS-150 150 A,

600 V, Class T

JJS-125 125 A,

600 V, Class T

n/a

FWH-200B 200 A,

500 V

JJS-150 150 A,

600 V, Class T

100

75

n/a

FWX-200A 200 A,

500 V

JJS-150 150 A,

600 V, Class T

n/a

FWH-250A 250 A,

500 V

JJS-175 175 A,

600 V, Class T

125

90

n/a

FWX-250A 250 A,

500 V

JJS-175 175 A,

600 V, Class T

n/a

n/a

n/a

Table 1.12 Fuse Replacement

For hp/kW sizes not shown in this chart, see the supplied FC 102, FC 202, or FC 302 Operating Instructions.

Installation Instructions

VLT® FC Series Internal Fuse Replacement

MI92D102 - VLT

®

 is a registered Danfoss trademark

5