22-44
Wake-up Ref./FB Difference
10 %
All set-ups
TRUE
0
Int8
22-45
Setpoint Boost
0 %
All set-ups
TRUE
0
Int8
22-46
Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-5* End of Curve
22-50
End of Curve Function
[0] Off
All set-ups
TRUE
-
Uint8
22-51
End of Curve Delay
10 s
All set-ups
TRUE
0
Uint16
22-6* Broken Belt Detection
22-60
Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61
Broken Belt Torque
10 %
All set-ups
TRUE
0
Uint8
22-62
Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
22-7* Short Cycle Protection
22-75
Short Cycle Protection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-76
Interval between Starts
300 s
All set-ups
TRUE
0
Uint16
22-77
Minimum Run Time
0 s
All set-ups
TRUE
0
Uint16
22-78
Minimum Run Time Override
[0] Disabled
All set-ups
FALSE
-
Uint8
22-79
Minimum Run Time Override
Value
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
22-8* Flow Compensation
22-80
Flow Compensation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-81
Square-linear Curve Approxi-
mation
100 %
All set-ups
TRUE
0
Uint8
22-82
Work Point Calculation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-83
Speed at No-Flow [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-84
Speed at No-Flow [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-85
Speed at Design Point [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-86
Speed at Design Point [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-87
Pressure at No-Flow Speed
0 N/A
All set-ups
TRUE
-3
Int32
22-88
Pressure at Rated Speed
999999 N/A
All set-ups
TRUE
-3
Int32
22-89
Flow at Design Point
0 N/A
All set-ups
TRUE
-3
Int32
22-90
Flow at Rated Speed
0 N/A
All set-ups
TRUE
-3
Int32
Table 4.19
4.1.19 23-** Time Based Funtions
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
23-0* Timed Actions
23-00
ON Time
ExpressionLimit
2 set-ups
TRUE
0
TimeOfDay-
WoDate
23-01
ON Action
[0] Disabled
2 set-ups
TRUE
-
Uint8
23-02
OFF Time
ExpressionLimit
2 set-ups
TRUE
0
TimeOfDay-
WoDate
23-03
OFF Action
[0] Disabled
2 set-ups
TRUE
-
Uint8
23-04
Occurrence
[0] All days
2 set-ups
TRUE
-
Uint8
23-1* Maintenance
23-10
Maintenance Item
[1] Motor bearings
1 set-up
TRUE
-
Uint8
23-11
Maintenance Action
[1] Lubricate
1 set-up
TRUE
-
Uint8
23-12
Maintenance Time Base
[0] Disabled
1 set-up
TRUE
-
Uint8
23-13
Maintenance Time Interval
1 h
1 set-up
TRUE
74
Uint32
23-14
Maintenance Date and Time
ExpressionLimit
1 set-up
TRUE
0
TimeOfDay
23-1* Maintenance Reset
23-15
Reset Maintenance Word
[0] Do not reset
All set-ups
TRUE
-
Uint8
Parameter Lists
VLT
®
Refrigeration Drive Programming Guide
184
MG16H102 - VLT
®
is a registered Danfoss trademark
4
4