4) Efficiency measured at nominal current. For energy efficiency class, see chapter 7.4 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
5) Measured using 5 m screened motor cables at rated load and rated frequency.
6) Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also chapter 3.7 Mechanical Planning.
7) Enclosure sizes B3+B4 and C3+C4 can be converted to IP21 using a conversion kit. See also chapter 3.7 Mechanical Planning.
7.2 Mains Supply
Mains supply
Supply terminals
L1, L2, L3
Supply voltage
200–240 V
±
10%
Supply voltage
380–480 V
±
10%
Supply voltage
525–600 V
±
10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the DC-link voltage drops below the
minimum stop level. The minimum stop level corresponds typically to 15% below the frequency converter's lowest rated supply
voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest
rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (
λ
)
≥
0.9 nominal at rated load
Displacement power factor (cos
ϕ
)
Near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW
Maximum 2 times/minutes
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW
Maximum 1 time/minute
Switching on input supply L1, L2, L3 (power-ups)
≥
90 kW
Maximum 1 time/2 minutes
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
7.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency (1.1–90 kW)
0–590
1)
Hz
Switching on output
Unlimited
Ramp times
1–3600 s
1) From software version 1.10 the output frequency of the frequency converter is limited to 590 Hz. Contact the local Danfoss
partner for further information.
Torque characteristics
Starting torque (constant torque)
Maximum 110% for 60 s
1)
Starting torque
Maximum 135% up to 0.5 s
1)
Overload torque (constant torque)
Maximum 110% for 60 s
1)
1) Percentage relates to the nominal torque.
Specifications
Design Guide
MG16G202
Danfoss A/S © 08/2015 All rights reserved.
121
7
7