Power
Size
Fuse options
Bussman
PN
Littelfuse PN Littelfuse
PN
Bussmann
PN
Siba PN
Ferraz-Shawmut
PN
Ferraz-Shawmut PN
(Europe)
Ferraz-Shawmut PN
(North America)
N110
170M2619 LA50QS300-4 L50S-300
FWH-300A 20 610
31.315
A50QS300-4
6.9URD31D08A0315
A070URD31KI0315
N132
170M2620 LA50QS350-4 L50S-350
FWH-350A 20 610
31.350
A50QS350-4
6.9URD31D08A0350
A070URD31KI0350
N160
170M2621 LA50QS400-4 L50S-400
FWH-400A 20 610
31.400
A50QS400-4
6.9URD31D08A0400
A070URD31KI0400
N200
170M4015 LA50QS500-4 L50S-500
FWH-500A 20 610
31.550
A50QS500-4
6.9URD31D08A0550
A070URD31KI0550
N250
170M4016 LA50QS600-4 L50S-600
FWH-600A 20 610
31.630
A50QS600-4
6.9URD31D08A0630
A070URD31KI0630
N315
170M4017 LA50QS800-4 L50S-800
FWH-800A 20 610
31.800
A50QS800-4
6.9URD32D08A0800
A070URD31KI0800
Table 10.6 Fuse Options for 380-480 V Adjustable Frequency Drives
OEM
Fuse options
VLT Model
Bussmann PN
Siba PN
Ferraz-Shawmut European PN
Ferraz-Shawmut North American PN
N75k T7
170M2616
20 610 31.160
6.9URD30D08A0160
A070URD30KI0160
N90k T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N110 T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N132 T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N160 T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N200 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N250 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N315 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N400 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
Table 10.7 Fuse Options for 525–690 V Adjustable Frequency Drives
For UL compliance, for units supplied without a contactor-
only option, the Bussmann 170M series fuses must be
used. See
for SCCR ratings and UL fuse criteria if
a contactor-only option is supplied with the adjustable
frequency drive.
10.3.3 Short Circuit Current Rating (SCCR)
If the adjustable frequency drive is not supplied with a line
power disconnect, contactor or circuit breaker, the Short
Circuit Current Rating (SCCR) of the adjustable frequency
drives is 100,000 amps at all voltages (380–690 V).
If the adjustable frequency drive is supplied with a line
power disconnect, the SCCR of the adjustable frequency
drive is 100,000 amps at all voltages (380–690 V).
If the adjustable frequency drive is supplied with a circuit
breaker, the SCCR depends on the voltage, see
415 V
480 V
600 V
690 V
D6h frame
100,000 A
100,000 A
65,000 A
70,000 A
D8h frame
100,000 A
100,000 A
42,000 A
30,000 A
Table 10.8
If the adjustable frequency drive is supplied with a
contactor-only option and is externally fused according to
, the SCCR of the adjustable frequency drive is as
follows:
Specifications
VLT
®
HVAC Drive D-Frame
Instruction Manual
MG16D222 - VLT
®
is a registered Danfoss trademark
10-9
10
10
Содержание VLT FC 100
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 110 400 kW D Frame VLT HVAC Drive FC 100...
Страница 2: ......
Страница 4: ...Safety VLT HVAC Drive D Frame Instruction Manual MG16D222 VLT is a registered Danfoss trademark...
Страница 8: ...Contents VLT HVAC Drive D Frame Instruction Manual MG16D222 VLT is a registered Danfoss trademark...
Страница 14: ...Introduction VLT HVAC Drive D Frame Instruction Manual 1 6 MG16D222 VLT is a registered Danfoss trademark 1 1...
Страница 40: ...Installation VLT HVAC Drive D Frame Instruction Manual 2 26 MG16D222 VLT is a registered Danfoss trademark 2 2...
Страница 58: ...Programming VLT HVAC Drive D Frame Instruction Manual 5 10 MG16D222 VLT is a registered Danfoss trademark 5 5...
Страница 98: ...www danfoss com drives MG16D222 130R0290 MG16D222 Rev 2012 12 14...