parameter 13-44 Logic Rule Boolean 3
. Define the operators
used to combine the selected inputs logically in
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-43 Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 4.18 Logic Rules
Priority of calculation
The results of
parameter 13-40 Logic Rule Boolean 1
,
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of
parameter 13-43 Logic Rule Operator 2
and
parameter 13-44 Logic Rule Boolean 3
, yielding the final
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[36]
Digital input DI29
[39]
Start command
[40]
Drive stopped
[42]
Auto Reset Trip
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-41 Logic Rule Operator 1
Option:
Function:
[0]
*
Disabled
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
Select the 2nd boolean (true or false)
input for the selected logic rule.
See
parameter 13-40 Logic Rule
Boolean 1
for further descriptions of
options and their functions.
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
Parameters
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
85
4