6.1.9 8-** Comm. and Options
Par.
No. #
Parameter description
Default value
4-set-up
Change during
operation
Conversion
index
Type
8-0* General Settings
8-01
Control Site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02
Control Source
ExpressionLimit
All set-ups
TRUE
-
Uint8
8-03
Control Timeout Time
1 s
1 set-up
TRUE
-1
Uint16
8-04
Control Timeout Function
[0] Off
1 set-up
TRUE
-
Uint8
8-07
Diagnosis Trigger
[0] Disable
1 set-up
TRUE
-
Uint8
8-1* Ctrl. Word Settings
8-10
Control Word Profile
[0] FC profile
All set-ups
TRUE
-
Uint8
8-14
Configurable Control Word CTW
[1] Profile default
All set-ups
TRUE
-
Uint8
8-19
Product Code
ExpressionLimit
1 set-up
TRUE
0
Uint32
8-3* FC Port Settings
8-30
Protocol
[0] FC
1 set-up
TRUE
-
Uint8
8-31
Address
1 N/A
1 set-up
TRUE
0
Uint8
8-32
Baud Rate
ExpressionLimit
1 set-up
TRUE
-
Uint8
8-33
Parity / Stop Bits
ExpressionLimit
1 set-up
TRUE
-
Uint8
8-35
Minimum Response Delay
0.01 s
1 set-up
TRUE
-3
Uint16
8-36
Maximum Response Delay
ExpressionLimit
1 set-up
TRUE
-3
Uint16
8-37
Maximum Inter-char delay
0.025 s
1 set-up
TRUE
-3
Uint16
8-4* FC MC protocol set
8-40
Telegram Selection
[1] Standard telegram 1
2 set-ups
TRUE
-
Uint8
8-42
PCD Write Configuration
ExpressionLimit
2 set-ups
TRUE
-
Uint8
8-43
PCD Read Configuration
ExpressionLimit
1 set-up
TRUE
-
uint8
8-5* Digital/Bus
8-50
Coasting Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-51
Quick Stop Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-52
DC Brake Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-53
Start Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-54
Reversing Select
[0] Digital input
All set-ups
TRUE
-
Uint8
8-55
Set-up Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-56
Preset Reference Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-57
Profidrive OFF2 Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-58
Profidrive OFF3 Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-7* BACnet
8-70
BACnet Device Instance
1 N/A
1 set-up
TRUE
0
Uint32
8-72
MS/TP Max Masters
127 N/A
1 set-up
TRUE
0
Uint8
8-73
MS/TP Max Info Frames
1 N/A
1 set-up
TRUE
0
Uint16
8-74
"I am" Service
[0] Send at power-up
1 set-up
TRUE
-
Uint8
8-75
Intialisation Password
[admin]
1 set-up
TRUE
0
VisStr[20]
8-79
Protocol Firmware version
ExpressionLimit
1 set-up
FALSE
-2
Uint16
8-8* FC Port Diagnostics
8-80
Bus Message Count
0 N/A
1 set-up
TRUE
0
Uint32
8-81
Bus Error Count
0 N/A
1 set-up
TRUE
0
Uint32
8-82
Slave Messages Rcvd
0 N/A
1 set-up
TRUE
0
Uint32
8-83
Slave Error Count
0 N/A
1 set-up
TRUE
0
Uint32
8-84
Slave Messages Sent
0 N/A
1 set-up
TRUE
0
Uint32
8-85
Slave Timeout Errors
0 N/A
1 set-up
TRUE
0
Uint32
8-88
Reset FC port Diagnostics
[0] Do not reset
1 set-up
TRUE
-
Uint8
8-9* Bus Jog / Feedback
8-90
Bus Jog 1 Speed
100 RPM
All set-ups
TRUE
67
Uint16
8-91
Bus Jog 2 Speed
200 RPM
All set-ups
TRUE
67
Uint16
Parameter Lists
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
133
6
6