6 Specifications
6.1 Clearances, Dimensions, and Weights
6.1.1 Clearances
To ensure sufficient air flow for the frequency converter, observe the minimum clearances listed in
.
When air flow is obstructed close to the frequency converter, ensure adequate inlet of cool air and exhaust of hot air from
the unit.
Enclosure
Power
1)
[kW (hp)]
Clearance at ends
[mm (in)]
Enclosure
size
Protection rating
3x380–480 V
Motor flange end
Cooling fan end
FCP 106
FCM 106
MH1
IP66/Type 4X
2)
IP55/Type 12
0.55–1.5 (0.75–2.0)
30 (1.2)
100 (4.0)
MH2
IP66/Type 4X
2)
IP55/Type 12
2.2–4.0 (3.0–5.0)
40 (1.6)
100 (4.0)
MH3
IP66/Type 4X
2)
IP55/Type 12
5.5–7.5 (7.5–10)
50 (2.0)
100 (4.0)
Table 6.1 Minimum Clearance for Cooling
1) Power ratings relate to NO, see chapter 6.2 Electrical Data.
2) The stated IP and Type rating only apply when the FCP 106 is mounted on a wall mount plate or a motor with the adapter plate. Ensure that
the gasket between the adapter plate and the motor has a protection rating corresponding to the required rating for the combined motor and
frequency converter. As standalone frequency converter, the enclosure rating is IP00 and Open type.
Enclosure size
Maximum depth of hole into adapter plate (A) [mm
(in)]
Maximum height of screw above adapter plate (B)
[mm (in)]
MH1
3 (0.12)
0.5 (0.02)
MH2
4 (0.16)
0.5 (0.02)
MH3
3.5 (0.14)
0.5 (0.02)
Table 6.2 Details for Motor Adapter Plate Screws
A
B
1
2
195NA494.10
1
Adapter plate
2
Screw
A
Maximum depth of hole into adapter plate
B
Maximum height of screw above adapter plate
Illustration 6.1 Screws to Fasten Motor Adapter Plate
Specifications
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
59
6
6