equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the frequency converter.
Before installing the frequency converter, check the
ambient air for liquids, particles, and gases. These checks
are done by observing existing installations in this
environment. Typical indicators of harmful airborne liquids
are water or oil on metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on instal-
lation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
3.6.5 Ambient Temperature
For recommended ambient temperature during storage
and operation, refer to
chapter 6.5 Ambient Conditions
and
chapter 6.10 Derating According to Ambient Temperature and
Switching Frequency
3.6.6 Acoustic Noise
FCP 106
Acoustic noise originates from the sources:
•
External fan.
•
DC intermediate circuit coils.
•
RFI filter choke.
Switching frequency
MH1
MH2
MH3
[kHz]
[dB]
[dB]
[dB]
5
55
55.5
52
Table 3.15 FCP 106 Acoustic Noise Levels, Fan on,
Measured 1 m from the Unit
FCM 106
Acoustic noise originates from the sources:
•
Motor fan.
•
External fan.
•
Motor stator and rotor.
•
DC intermediate circuit coils.
•
RFI filter choke.
Motor
speed
Switching
frequency
Fan
MH1
MH2
MH3
[RPM]
[kHz]
[on/off]
[dB]
[dB]
[dB]
0
5
on
55
55.5
52
150
5
off
57.5
50
57
150
5
on
61
57
59
1500
5
off
65.5
64
71.5
1500
5
on
66
65.5
71.5
1500
10
off
65
61.5
66.5
Motor
speed
Switching
frequency
Fan
MH1
MH2
MH3
[RPM]
[kHz]
[on/off]
[dB]
[dB]
[dB]
1500
16
off
64
60
65.5
1500
16
on
64.5
62
65.5
Table 3.16 FCM 106 Acoustic Noise Levels,
Measured 1 m from the Unit
3.6.7 Vibration and Shock
The frequency converter complies with requirements for
wall- or floor-mounted units mounted at production
premises, as well as in panels bolted to walls or floors.
The frequency converter has been tested according to the
procedures defined in
IEC 61800-5-1 Ed.2
Vibration test, Cl. 5.2.6.4
IEC/EN 60068-2-6
Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64
Vibration, broad-band random
IEC 60068-2-34,
60068-2-35, 60068-2-36
Curve D (1–3) Long-term test 2.52 g
RMS
Table 3.17 Vibration and Shock Test Procedure Compliance
System Integration
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
43