8-35 Minimum Response Delay
Range:
Function:
overcoming modem turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Size
related
*
[ 0.1 -
10.0 s]
Specify the maximum permissible
delay time between receiving a
request and transmitting the response.
If this time is exceeded, no response is
returned.
6.2.3 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus
merging.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
[0]
Digital
input
Activates coast via a digital input.
[1]
Bus
Activates coast via the serial communication
port.
[2]
Logic
AND
Activates coast via the fieldbus/serial communi-
cation port, AND additionally via one of the
digital inputs.
[3]
*
Logic OR Activates coast via the serial communication port
OR via one of the digital inputs.
8-51 Quick Stop Select
Option:
Function:
Select control of the Quick Stop function via the
terminals (digital input) and/or via the bus.
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word.
[0]
Digital
input
Activates Quick Stop via a digital input.
[1]
Bus
Activates Quick Stop via the serial communi-
cation port.
8-51 Quick Stop Select
Option:
Function:
[2]
Logic
AND
Activates Quick Stop via the serial communi-
cation port, AND additionally via one of the
digital inputs.
[3]
*
Logic OR Activates Quick Stop via the serial communi-
cation port OR via one of the digital inputs.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input).
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
[0] Digital
input
Activates DC brake via a digital input.
[1] Bus
Activates DC brake via the serial communication
port.
[2] Logic
AND
Activates DC brake via the serial communication
port, AND additionally via one of the digital
inputs.
[3] Logic OR Activates DC brake via the serial communication
port OR via one of the digital inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input).
NOTICE
This parameter is active only when
is set to
[0]
Digital and control wor
d.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communi-
cation port.
[2]
Logic
AND
Activates Start command via the serial communi-
cation port, AND additionally via one of the
digital inputs.
[3]
*
Logic OR Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
8-54 Reversing Select
Option:
Function:
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the serial communication port.
Parameters
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
22
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.
6
6