background image

6.5.12 Relay Outputs, Enclosure Size H6

Programmable relay output

2

Relay 01 and 02

01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)

Maximum terminal load (AC-1)

 (1) 

on 04–05 (NO) (resistive load)

 (2) (3)

400 V AC, 2 A

Maximum terminal load (AC-15)

 (1) 

on 04–05 (NO) (Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Maximum terminal load (DC-1)

 (1) 

on 04–05 (NO) (Resistive load)

80 V DC, 2 A

Maximum terminal load (DC-13)

 (1) 

on 04–05 (NO) (Inductive load)

24 V DC, 0.1 A

Maximum terminal load (AC-1)

 (1) 

on 04–06 (NC) (Resistive load)

240 V AC, 4 A

Maximum terminal load (AC-15)

 (1) 

on 04–06 (NC) (Inductive load @ cosφ 0.4)

240 V AC, 0.2 A

Maximum terminal load (DC-1)

 (1) 

on 04–06 (NC) (Resistive load)

50 V DC, 2 A

Maximum terminal load (DC-13)

 (1) 

on 04–06 (NC) (Inductive load)

24 V DC, 0.1 A

Minimum terminal load on 01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)

24 V DC 10 mA, 24 V AC 20 mA

Environment according to EN 60664-1

Overvoltage category III/pollution degree 2

2

Overvoltage Category II.

3

UL applications 300 V AC 2 AC.

6.5.13 Control Card, 10 V DC Output

Terminal number

50

Output voltage

10.5 V ±0.5 V

Maximum load

25 mA

6.5.14 Ambient Conditions

Enclosure protection rating

IP20

Enclosure kit available

IP21, TYPE 1

Vibration test

1.0 g

Maximum relative humidity

5–95% (IEC 60721-3-3; Class 3K3 (non-condensing)

during operation)

Aggressive environment (IEC 60721-3-3), coated (standard), enclosure sizes
H3–H5

Class 3C3

Aggressive environment (IEC 60721-3-3), non-coated enclosure size H6

Class 3C2

Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature, enclosure sizes H3–H5

 (1)

50 °C (122 °F)

Ambient temperature, enclosure size H6

45 °C (113 °F)

Minimum ambient temperature during full-scale operation

0 °C (32 °F)

Minimum ambient temperature at reduced performance, enclosure sizes H3–
H5

-20 °C (-4 °F)

Minimum ambient temperature at reduced performance, enclosure size H6

-10 °C (14 °F)

Temperature during storage/transport

-30 to +65/70 °C (-22 to +149/158°F)

Maximum altitude above sea level without derating

1000 m (3281 ft)

Maximum altitude above sea level with derating

3000 m (9843 ft)

Specifications

Operating Guide  | VLT® Compressor Drive CDS 803

AQ321748767627en-000101 / 130R0570| 49

Danfoss A/S © 2019.12

Содержание VLT CDS 803

Страница 1: ...Operating Guide VLT Compressor Drive CDS 803...

Страница 2: ......

Страница 3: ...rid 12 3 2 3 Mains and Motor Connection 13 3 2 3 1 Introduction 13 3 2 3 2 Connecting to Mains and Motor 14 3 2 3 3 Relays and Terminals on Enclosure Sizes H3 H5 17 3 2 3 4 Relays and Terminals on Enc...

Страница 4: ...ions 45 6 4 1 Derating for Ambient Temperature and Switching Frequency 45 6 4 2 Derating for Low Air Pressure and High Altitudes 45 6 5 General Technical Data 46 6 5 1 Protection and Features 46 6 5 2...

Страница 5: ...l Tool MCT 10 software support Download the software from the Service and Support download page on www danfoss com During the installation process of the software enter CD key 34544400 to activate the...

Страница 6: ...or systems that have to be compliant with UL IEC EN 60335 For more information on UL 508C thermal memory retention requirements refer to the section Motor Thermal Protection in the product specific de...

Страница 7: ...ngineers or persons who have received training from qualified electrical engineers and are suitably experienced to operate devices systems plant and machinery in accordance with pertinent laws and reg...

Страница 8: ...time after power has been removed before performing service or repair work could result in death or serious injury Stop the motor Disconnect AC mains permanent magnet type motors and remote DC link s...

Страница 9: ...HAZARD An internal failure in the drive can result in serious injury when the drive is not properly closed Ensure that all safety covers are in place and securely fastened before applying power 2 4 Mo...

Страница 10: ...8 H5 17 TR VZH117 H5 26 TRVZH170 H6 3 1 2 Side by side Installation The drive can be mounted side by side but requires the clearance specified in table 6 above and below for cooling Table 6 Clearance...

Страница 11: ...4 2 9 H4 IP20 6 0 7 5 8 0 10 10 15 296 11 7 359 14 1 275 10 8 135 5 3 105 4 1 H5 IP20 10 15 18 5 22 25 30 334 13 1 402 15 8 314 12 4 150 5 9 120 4 7 H6 IP20 30 40 518 20 4 595 23 4 635 25 45 kW 495 19...

Страница 12: ...ec tion rat ing 3x200 240 V 3x380 480 V Mains Motor DC con nection Control ter minals Ground Relay H3 IP20 6 0 7 5 8 0 10 0 8 7 0 8 7 0 8 7 0 5 4 0 8 7 0 5 4 H4 IP20 6 0 7 5 8 0 10 10 15 15 20 1 2 11...

Страница 13: ...ly with EMC emission specifications and connect this cable to both the decoupling plate and the motor Keep the motor cable as short as possible to reduce the noise level and leakage currents For furth...

Страница 14: ...late into place and tighten fully DC DCBR BR UV W 9 9 M A I N S 95 RELA Y 1 RELA Y 2 L C e30ba261 10 2 Mount the ground cables to the ground terminal before mounting other cables Installation Operatin...

Страница 15: ...or to terminals U V and W and then tighten the screws according to the torques described in 3 2 1 Electrical Installation in General MOTOR MOTOR U VW 99 e30bt302 12 Installation Operating Guide VLT Co...

Страница 16: ...ply to terminals L1 L2 and L3 and then tighten the screws according to the torques e30ba263 10 95 M A INS DC BR BR U V W 91 92 93 L1 L2 L3 RELA Y 1 RELA Y 2 5 Tighten support bracket on mains wires In...

Страница 17: ...r U V W DC DC MAINS 1 Mains 3 Compressor 2 Ground 4 Relays Illustration 7 Enclosure Sizes H3 H5 IP20 200 240 V 6 0 10 kW 8 0 15 hp IP20 380 480 V 6 0 22 kW 8 0 30 hp Installation Operating Guide VLT C...

Страница 18: ...the fuses and circuit breakers listed in this chapter to protect service personnel or other equipment in case of an internal failure in the unit or a short circuit on the DC link The drive provides f...

Страница 19: ...480 V IP20 6 0 8 0 FRS R 25 KTS R25 JKS 25 JJS 25 25 7 5 10 FRS R 25 KTS R25 JKS 25 JJS 25 25 10 15 FRS R 50 KTS R50 JKS 50 JJS 50 50 18 5 25 FRS R 80 KTS R80 JKS 80 JJS 80 63 22 30 FRS R 80 KTS R80 J...

Страница 20: ...la tion stripped Output con tactor Motor cable Motor 3 phases and PLC Panel Mains supply Minimum 200 mm 7 87 in between control cable mains cable and between mains motor cable PLC protective earth Rei...

Страница 21: ...6 2 Setting the Control Terminals to Run the Compressor Context e30bb625 11 12 20 55 20 27 29 42 45 55 50 53 54 GND GND DIGI IN OUT DIGI IN OUT 61 68 69 N P COMM GND 24 V DIGI IN DIGI IN 10 V 20 mA I...

Страница 22: ...20 mA 0 4 20 mA 42 0 4 20 mA A OUT D OUT 45 0 4 20 mA A OUT D OUT 18 D IN 19 D IN 27 D IN OUT 29 D IN OUT 12 24 V OUT 24 V NPN 20 COM D IN O V PNP 24 V NPN O V PNP 24 V NPN O V PNP 24 V NPN O V PNP B...

Страница 23: ...TICE There is no access to UDC and UDC on the following units IP20 380 480 V 30 kW 40 hp Installation Operating Guide VLT Compressor Drive CDS 803 AQ321748767627en 000101 130R0570 23 Danfoss A S 2019...

Страница 24: ...is illuminated with 2 alphanumeric lines All data is shown on the LCP The illustration 13 describes the information that can be read from the display Table 12 Legend to Section A 1 Parameter number a...

Страница 25: ...e used for setting local reference 12 OK For selecting a parameter and for accepting changes to parameter settings D Operation keys and indicator lights Table 14 Legend to Section D 13 Hand On Starts...

Страница 26: ...50 Hz IT grid 1 200 240 V 50 Hz Delta 2 200 240 V 50 Hz 10 380 440 V 50 Hz IT grid 11 380 440 V 50 Hz Delta 12 380 440 V 50 Hz 20 440 480 V 50 Hz IT grid 21 440 480 V 50 Hz Delta 22 440 480 V 50 Hz 30...

Страница 27: ...60 Main Menu Pass word 0 999 0 Define the password for access to the LCP Parameter 1 13 Compressor Se lection 24 VZH028 R410A 25 VZH035 R410A 26 VZH044 R410A 27 VLZ028 28 VLZ035 29 VLZ044 30 VZH088 31...

Страница 28: ...oast and reset inverse 4 Quick stop inverse 5 DC brake inverse 6 Stop inverse 7 External Interlock 8 Start 9 Latched start 10 Reversing 11 Start reversing 14 Jog 16 Preset ref bit 0 17 Preset ref bit...

Страница 29: ...orresponds to the low reference value Parameter 6 11 Terminal 53 High Voltage 0 10 V 10 V Enter the voltage that corresponds to the high reference value Parameter 8 01 Control Site 0 Digital and ctrl...

Страница 30: ...terval between Starts 0 3600 s 300 s Enter the minimum allowed time between starts Parameter 28 02 Minimum Run Time 10 3600 s 60 s Enter the minimum allowed time to run before stop Parameter 28 10 Oil...

Страница 31: ...ration Mode Open loop 3 03 Maximum Reference 200 000 3 42 Ramp 1 Ramp Down Time 5 5 12 Terminal 27 Digital Input 3 41 Ramp 1 Ramp Up Time 5 6 7 8 9 10 11 12 3 15 Reference 1 Source 6 14 Terminal 53 Lo...

Страница 32: ...z Delta 2 200 240 V 50 Hz 10 380 440 V 50 Hz IT grid 11 380 440 V 50 Hz Delta 12 380 440 V 50 Hz 20 440 480 V 50 Hz IT grid 21 440 480 V 50 Hz Delta 22 440 480 V 50 Hz 30 525 600 V 50 Hz IT grid 31 52...

Страница 33: ...ord for access to the LCP Parameter 1 00 Configuration Mode 0 Open loop 3 Closed loop 0 Open loop Select closed loop Parameter 1 13 Compressor Se lection 24 VZH028 R410A 25 VZH035 R410A 26 VZH044 R410...

Страница 34: ...42 Ramp 1 Ramp Down Time 0 05 3600 0 s 30 00 s Ramp down time from nominal motor speed to 0 Parameter 5 12 Terminal 27 Digital Input 0 No operation 1 Reset 2 Coast inverse 3 Coast and reset inverse 4...

Страница 35: ...e Parameter 6 11 Terminal 53 High Voltage 0 10 V 10 V Enter the voltage to the high reference val ue Parameter 6 14 Terminal 53 Low Ref Feedb Value 4999 to 4999 Size related Enter the reference value...

Страница 36: ...aud 7 115200 Baud 2 9600 Baud Select the baud rate for the RS485 port Parameter 20 00 Feedback 1 Source 0 No function 1 Analog Input 53 2 Analog Input 54 3 Pulse input 29 100 Bus Feedback 1 101 Bus Fe...

Страница 37: ...g 7 Press OK to accept the change 8 Press either Back twice to enter Status or press Menu once to enter the Main Menu 4 7 Accessing All Parameter via the Main Menu Procedure 1 Press Menu until the ind...

Страница 38: ...10 Terminal 18 Digital Input 5 11 Terminal 19 Digital Input 5 12 Terminal 27 Digital Input 5 13 Terminal 29 Digital Input 5 4 Relays 5 40 Function Relay 5 41 On Delay Relay 5 42 Delay Relay 5 5 Pulse...

Страница 39: ...6 61 Terminal 53 Setting 16 62 Analog input 53 16 63 Terminal 54 Setting 16 64 Analog input 54 16 65 Analog output 42 mA 16 66 Digital Output 16 67 Pulse input 29 Hz 16 71 Relay output 16 72 Counter A...

Страница 40: ...over load X X More than 100 load for a long time 10 8 Motor ETR over X X For 6 0 10 kW 8 0 15 hp drives The motor is too hot due to more than 100 load for a long time See parame ter 1 90 Motor Therma...

Страница 41: ...gain some times until the AMA is carried out NOTICE Repeated runs may heat the motor to a level where the resistance Rs and Rr are increased Usu ally however this is not critical 58 AMA internal X X C...

Страница 42: ...d rotor X The rotor is locked or the load is too high 126 Motor Rotating X High back EMF voltage Stop the rotor of the PM motor 200 Fire Mode X Fire mode has been activated 202 Fire Mode Lim its Excee...

Страница 43: ...ection IP20 kg lb 7 9 17 4 7 9 17 4 9 5 21 Efficiency best case typical 1 97 3 97 98 5 97 1 97 2 97 1 1 At rated load conditions 6 2 Mains Supply 3x380 480 V AC Table 20 3x380 480 V AC Drive 4 TR VZH0...

Страница 44: ...IP20 kg lb 4 3 9 5 4 3 9 5 7 9 17 4 9 5 20 9 9 5 20 9 24 5 54 Efficiency best case typical 2 98 4 98 98 2 97 8 98 1 97 9 98 1 97 9 98 1 97 9 97 8 1 Applies for dimensioning of drive cooling If the swi...

Страница 45: ...A1 EN IEC61800 3 C2 6 0 10 kW 8 0 15 hp 3x200 240 V IP20 25 82 50 164 20 66 Yes Yes No H2 RFI filter EN 55011 A2 EN IEC 61800 3 C3 18 30 kW 25 40 hp 3x380 480 V IP20 5 16 4 Yes No No 6 4 Special Condi...

Страница 46: ...L3 power ups Maximum 2 times minute Environment according to EN 60664 1 Overvoltage category III pollution degree 2 The unit is suitable for use on a circuit capable of delivering not more than 10000...

Страница 47: ...53 mode Parameter 6 61 Terminal 53 Setting 1 voltage 0 current Terminal 54 mode Parameter 6 63 Terminal 54 Setting 1 voltage 0 current Voltage level 0 10 V Input resistance Ri Approximately 10 k Maxim...

Страница 48: ...03 NC 01 02 NO 04 06 NC 04 05 NO Maximum terminal load AC 1 1 on 01 02 04 05 NO Resistive load 250 V AC 3 A Maximum terminal load AC 15 1 on 01 02 04 05 NO Inductive load cos 0 4 250 V AC 0 2 A Maxim...

Страница 49: ...Card 10 V DC Output Terminal number 50 Output voltage 10 5 V 0 5 V Maximum load 25 mA 6 5 14 Ambient Conditions Enclosure protection rating IP20 Enclosure kit available IP21 TYPE 1 Vibration test 1 0...

Страница 50: ...perature Derating for high altitude 2 Determined according to EN 50598 2 at Rated load 90 rated frequency Switching frequency factory setting Switching pattern factory setting NOTICE The VLT Compresso...

Страница 51: ...Installation Qualified personnel 7 L LCP 24 Leakage current 8 Local control panel 24 Low air pressure 45 M Mains supply L1 L2 L3 46 MCT 10 setup software 24 Menu key 25 Motor output U V W 46 Motor ov...

Страница 52: ...UL Non UL compliance 19 V Voltage Safety warning 7 W Website 5 Wiring schematic 22 Index Operating Guide VLT Compressor Drive CDS 803 AQ321748767627en 000101 130R0570 52 Danfoss A S 2019 12...

Страница 53: ...Operating Guide VLT Compressor Drive CDS 803 AQ321748767627en 000101 130R0570 53 Danfoss A S 2019 12...

Страница 54: ...der provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies D...

Отзывы: