4 Specifications
4.1 Electrical Data
4.1.1 Electrical Data 3x200–240 V AC
Table 4: 3x200–240 V AC
P6K0
P7K5
P10K
Typical shaft output [kW]
6.0
7.5
10
Typical shaft output [hp]
8.0
10
15
Enclosure size
H4
H4
H5
Maximum cable size in terminals (mains, compressor) [mm
2
(AWG)]
16 (6)
16 (6)
16 (6)
Output current @ 40 °C (104 °F) ambient temperature
Continuous (3x200–240 V) [A]
22
28
42
Intermittent (3x200–240 V) [A]
24.2
30.8
46.2
Output current @ 50 °C (122 °F) ambient temperature
Continous (3x200–240 V) [A]
19.8
23
33
Intermittent (3x200–240 V) [A]
21.8
25.3
36.3
Maximum input current
Continuous (3x200–240 V) [A]
21
28.3
41
Intermittent (3x200–240 V) [A]
23.1
31.1
45.1
Maximum mains fuses, see
6.2.1 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best case/typical
(1)
182/204
229/268
369/386
Weight enclosure protection IP20 [kg (lb)]
7.9 (17.4)
7.9 (17.4)
9.5 (22.9)
Efficiency [%], best case/typical
(2)
97.3/97.1
98.5/97.1
97.2/97.1
1
Applies to dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
4.1.2 Electrical Data 3x380–480 V AC
Table 5: 3x380–480 V AC
P6K0
P7K5
P10K
P18K
P22K
P30K
Typical shaft output [kW]
6.0
7.5
10
18.5
22
30
Typical shaft output [hp]
8.0
10
15
25
30
40
Enclosure size
H3
H3
H4
H5
H5
H6
Maximum cable size in terminals (mains, motor) [mm
2
(AWG)]
4 (10)
4 (10)
16 (6)
16 (6)
16 (6)
35 (2)
AJ330233902305en-000201 / 130R0596 | 27