6 Electrical Installation Considerations
6.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors
are required. 75 °C (167 °F) is recommended.
6.1.1 Fastener Torque Ratings
Table 14: Tightening Torques for Enclosure Sizes H3–H6, 3x200–240 V & 3x380–480 V
Power [kW (hp)]
Torque [Nm (in-lb)]
Enclo-
sure size
IP protec-
tion rat-
ing
3x200–240 V
3x380–480 V
Mains
Motor
DC connec-
tion
Control ter-
minals
Ground Relay
H3
IP20
–
6.0–7.5 (8.0–10) 0.8 (7)
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
H4
IP20
6.0–7.5 (8.0–
10)
10–15 (15–20)
1.2 (11) 1.2 (11) 1.2 (11)
0.5 (4)
0.8 (7)
0.5 (4)
H5
IP20
10 (15)
18.5–22 (25–30) 1.2 (11) 1.2 (11) 1.2 (11)
0.5 (4)
0.8 (7)
0.5 (4)
H6
IP20
–
30 (40)
4.5 (40) 4.5 (40) –
0.5 (4)
3 (27)
0.5 (4)
6.2 Fuses and Circuit Breakers
Fuses and circuit breakers ensure that possible damage to the drive is limited to damage inside the unit. Danfoss recommends fuses
on the supply side as protection. For further information, see the application note Fuses and Circuit Breakers found on
Service and support/Documentation/Manuals & guides
.
N O T I C E
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
6.2.1 Recommendation of Fuses and Circuit Breakers
Table 15: Fuses and Circuit Breakers
Circuit breakers
(1)
Fuse
UL
Non-UL
UL
Non-UL
Bussmann
Bussmann
Bussmann
Bussmann
Maximum fuse
Power [kW (hp)]
Type RK5
Type RK1
Type J
Type T
Type gG
3x200–240 V
6.0 (8.0)
–
–
FRS-R-50
KTN-R50
JKS-50
JJN-50
gG-50
7.5 (10)
FRS-R-50
KTN-R50
JKS-50
JJN-50
gG-50
10 (15)
FRS-R-80
KTN-R80
JKS-80
JJN-80
gG-63
3x380–480 V
6.0 (8.0)
–
–
FRS-R-25
KTS-R25
JKS-25
JJS-25
gG-25
7.5 (10)
FRS-R-25
KTS-R25
JKS-25
JJS-25
gG-25
10 (15)
FRS-R-50
KTS-R50
JKS-50
JJS-50
gG-50
AJ330233902305en-000201 / 130R0596 | 45