VLT

®

 AutomationDrive EtherNet/IP 

 

 

 

 

 

MG.90.Jx.02 ver. 5

th

 September 2007 – VLT is a registered Danfoss trademark 

52

 

Class ID 0x29 Control Supervisor Object 

Instance Attributes 

Attribute 

Access 

Name 

Data Type 

Description 

Get 

Number of Attributes 
supported 

USINT 12 

Get 

List of supported 
Attributes 

Array of 

USINT 

3,4,4,5,6,7,8,9,10,11,12,13,15 

Get/Set 

Run 1 (forward) 

Boolean 

FC CTW Bit 6 = Run1 XOR Run2 
FC CTW Bit15 = 0 

Get/Set 

Run 2 (reverse) 

Boolean 

FC CTW Bit 6 = Run1 XOR Run2 
FC CTW Bit15 = 1 

Get/Set 

Network Control 

Boolean 

Parameter 12-32 value written from option 

Get 

State 

USINT 

The state of the CIP state-machine 

Get 

Running 1 

Boolean 

Run1 AND bit 11 in FC STW 

Get 

Running 2 

Boolean 

Run2 AND bit 11 in FC STW 

Get 

Ready 

Boolean 

STATE_ENABLED or STATE_STOPPING or 
STATE_FAULT_STOP from state-machine 

10 

Get 

Faulted 

Boolean 

Bit 3 in FC STW 

11 

Get 

Warning 

Boolean 

Bit 7 in FC STW 

12 

Get/Set 

Fault reset 

Boolean 

Bit 7 in FC CTW 

13 

Get 

Fault Code 

UINT 

Mapping of par. 16-90 Alarm Word to CIP 
specific fault codes 

15 

Get 

Control from net 

Boolean 

Parameter 12-31 value written from option 

 

 

Attribute 13 “Fault Code” 

CIP Malfunction 
Code 

Meaning 

VLT-Code 
Alarmword 

CIP Malfunction 
Meaning 

CIP 
Classification 

No alarm 

0000 0000 

No fault 

unused 

0000 0001 

No fault 

4210 

Drive over temperature 

0000 0002 

Excessive Device 
Temperature 

mar 

2240 

Earth fault 

0000 0004 

Short to earth 

mau 

unused 

0000 0008 

No fault 

8100 Controlword 

timeout 0000 

0010 

Communication 

mir 

2310 

Overcurrent 

0000 0020 

Continuous Overcurrent  mau 

8302 

Torque limit 

0000 0040 

Torque limiting 

mar 

4310 

Motor thermistor 

0000 0080 

Excess Drive 
Temperature 

mar 

4310 

Motor ETR over temp 

0000 0100 

Excess Drive 
Temperature 

mar 

2311 

Inverter overloaded 

0000 0200 

Current inside the 
device, No. 1 

mar 

3220 

DC Link undervoltage 

0000 0400 

Undervoltage inside the 
Device 

mar 

3210 

DC Link overvoltage 

0000 0800 

Overvoltage inside the 
device 

mar 

2130 

Short circuiting 

0000 1000 

Short Circuit 

mau 

2213 

Inrush fault 

0000 2000 

Overcurr. during startup  mar 

3130 

Mains phase loss 

0000 4000 

Phase Failure 

mau 

5210 

AMT fail 

0000 8000 

Measurement Circuit 

mir 

1000 

Live zero fault 

0001 0000 

General fault 

mar 

6100 

Internal fault 

0002 0000 

Internal software fault 

mau 

7110 

Brake resistor power limit 

0004 0000 

Brake Chopper 

mau 

3300 

Motor phase U missing 

0008 0000 

Output voltage 

mau 

3300 

Motor phase V missing 

0010 0000 

Output voltage 

mau 

3300 

Motor phase W missing 

0020 0000 

Output voltage 

mau 

8100 

Fieldbus Comm. fault 

0040 0000 

Communication 

mir 

5112 

24V supply fault 

0080 0000 

+24V Power supply 

mau 

3100 

Mains failure 

0100 0000 

Mains Voltage 

mar 

5110 

1,8V supply fault 

0200 0000 

Low voltage power 
supp. 

mau 

7110 

Brake resist. short circ. 

0400 0000 

Brake chopper 

mar 

7110 

Brake chopper fault 

0800 0000 

Brake chopper 

mar 

Содержание VLT AutomationDrive

Страница 1: ...3 Network 3 Recommended Design Rules 3 EMC Precautions 3 How to Install Option in Frequency Converter 3 How to Configure the System 3 IP Settings 3 Ethernet Link Parameters 3 Configuring the Scanner 3...

Страница 2: ...software environment Although Danfoss A S has tested and reviewed the documentation within this manual Danfoss A S makes no warranty or representation either express or implied with respect to this do...

Страница 3: ...ss 20 motor overload protection in accordance with NEC 6 Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains Check that the mains supply has been...

Страница 4: ...tem For more detailed information including the full range of set up options and diagnosis tools please refer to the chapters How to Configure the System How to Control the FC 300 How to Access FC 300...

Страница 5: ...h a Danfoss FC 300 frequency converter It is also assumed that the installed controller supports the interfaces described in this document and that all the requirements stipulated in the controller as...

Страница 6: ...erNet IP EMC Electromagnetic Compatibility I O Input Output IP Internet Protocol LCP Local Control Panel LED Light Emitting Diode LSB Least Significant Bit MAV Main Actual Value actual output MSB Most...

Страница 7: ...2007 VLT is a registered Danfoss trademark 7 How to Install The EtherNet IP Option The option has 3 bi coloured LED s according to ODVA specifications LED label Description MS Module Status NS1 Netwo...

Страница 8: ...test Red Green Flashing red green The EIP option is in self test mode NS1 NS2 Network status one per port State LED Description No IP address no power Off The device does not have a valid IP address...

Страница 9: ...to the typical star topology The two ports are equal in the sense that they are transparent for the option If only one connector is used either port can be used Star topology Line topology Automation...

Страница 10: ...hat the medias chosen for Ethernet data transmission are suitable Usually CAT 5e and 6 cables are recommended for industrial applications Both types of cable are available as Unshielded Twisted Pair a...

Страница 11: ...IP the maximum number of drives in a line is dependent of the API speed of the connected scanner According to the graph above the network should thus be segmented with the use of external Ethernet swi...

Страница 12: ...ding protective earth connection must be observed The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to th...

Страница 13: ...ures Instructions Remove LCP panel from the FC 300 Remove the frame located beneath and discard Push the option into place The Ethernet connectors must be facing upwards Push the fieldbus option adapt...

Страница 14: ...ubnet Mask 12 07 Domain Name 12 03 Default Gateway 12 08 Host Name 12 04 DHCP Server 12 09 Physical Address The MCA121 option offers several ways of IP address assignment Setting up drive with manual...

Страница 15: ...remaining lease time can be read out in par 12 05 Lease Expires Par 12 09 Physical Address reads out the MAC address of option which is also printed on the label of the option If using fixed leases t...

Страница 16: ...rnet devices to choose common transmission parameters such as speed and duplex mode In this process the connected devices first share their capabilities as for these parameters and then choose the fas...

Страница 17: ...utions Softwaredownload DDFieldbus_Setup_Files htm N B The current version of the major EtherNet IP configuration tools does not support EDS files for EtherNet IP devices Configuring a Rockwell Master...

Страница 18: ...ection Tab enter information about RII and fault conditions The Module Info tap holds generic information The Reset Module button will make a simulated Power cycle of the drive N B For more informatio...

Страница 19: ...ulticast traffic to all connected hosts IGMP IGMP Internet Group Management Protocol is an integrated part of IP It allows hosts to join or leave a multicast host group Group membership information is...

Страница 20: ...101 153 8 bytes 20 bytes It is not possible to mix instances across profiles e g 20 100 Assembly instances must consistent to the profile ODVA or FC profile The controlling instance can be read in pa...

Страница 21: ...arget Target to Originator Point to Point Multicast Target to Originator only Data Size Specified in bytes for both directions Originator Target Target Originator The data size depends on the assembly...

Страница 22: ...taining theses information Connection Name Given name for connection Message Parameters Service Code Class Instance Attribute Member Request Data Unconnected Messages UCMM Non cyclic single connection...

Страница 23: ...the inserting of COS filters par 12 21 to 12 21 for each bit in the different PCD words The filter acts like a logical AND function If a bit in the filter is set to 1 the COS function triggers upon a...

Страница 24: ...define how Bit 03 gates with the corresponding function on a digital input Bit 04 Quick stop Bit 04 0 causes a stop in which the motor speed is ramped down to stop via par 3 81 Quick stop ramp time B...

Страница 25: ...sed so this function is useful for turning off the control word when not required for updating or reading parameters Bit 11 Relay 01 Bit 11 0 Relay not activated Bit 11 1 Relay 01 activated provided C...

Страница 26: ...required to re establish operation Bit 04 No error error no trip Bit 04 0 means that the frequency converter is not in fault mode Bit 04 1 means that there is a frequency converter error but no trip B...

Страница 27: ...K limit exceeded Bit 13 0 means that there are no voltage warnings Bit 13 1 means that the DC voltage in the frequency converter s intermediate circuit is too low or too high Bit 14 Torque OK limit ex...

Страница 28: ...Net Ref 07 15 Explanation of the Bits Bit 0 Run Fwd Bit 0 0 means that the VLT frequency converter has a stop command Bit 0 1 leads to a start command and the VLT frequency converter will start to run...

Страница 29: ...of the control word are set at the same time Bit 3 Running 2 Bit 3 0 means that the drive is in neither of these states or that Run 2 is not set Bit 3 1 means that the drive state attribute is enable...

Страница 30: ...ce Forward Forward Reverse Par 3 00 set to 1 Max Max Par 3 00 set to 0 Min Max The actual reference Ref in the VLT depends on the settings in the following parameters Parameter 1 23 Motor frequency Pa...

Страница 31: ...mber 2007 VLT is a registered Danfoss trademark 31 Bus Speed Reference Value under Instances 20 70 and 21 71 Master slave 16 bit CTW Speed ref RPM The speed reference value should be transmitted to th...

Страница 32: ...set to 3 Option A to enable control from the EtherNet IP option This parameter cannot be adjusted while the motor is running 8 03 Control Word Timeout Time Range 0 1 18000 0 s 1 0 s Function Enter the...

Страница 33: ...displays a warning until par 8 06 toggles Then the frequency converter resumes its original set up Resume The frequency converter resumes the set up active prior to the time out 8 06 Reset Control Wor...

Страница 34: ...en par 8 01 Control site is set to 0 Digital and control word 8 51 Quick Stop Select Option Digital input 0 Bus 1 Logic AND 2 Logic OR 3 Function Select control of the Quick Stop function via the term...

Страница 35: ...via the terminals digital input and or via the fieldbus N B This parameter is active only when par 8 01 Control site is set to 0 Digital and control word 8 56 Preset Reference Select Option Digital in...

Страница 36: ...he option Read only if par 12 00 set to DHCP or BOOTP 12 04 DHCP Server Option 000 000 000 000 255 255 255 255 Function Read only Displays the IP address of the found DHCP or BOOTP server N B A power...

Страница 37: ...h port in dd hh mm ss 12 12 Auto Negotiation Option Off 0 On 1 Function Configures Auto Negotiation of Ethernet link parameters for each port ON or OFF If set to OFF Link Speed and Link Duplex can con...

Страница 38: ...Configuration of readable process data N B For configuration of 2 word 32 bit parameter read write use 2 consecutive arrays in par 12 21 and 12 22 12 28 Store Data Values Option Off 0 Store All set u...

Страница 39: ...ction Read only Displays the control source in Instance 21 71 Off Control via the network is not active On Control via the network is active 12 33 CIP Revision Range 0 Major version 00 99 1 Minor vers...

Страница 40: ...Server Option Disable 0 Enable 1 Function Enables disables the build in HTTP web server 12 82 SMTP service Option Disable 0 Enable 1 Function Enables disables the SMTP e mail service on the option 12...

Страница 41: ...2 0 200m Function If Cable Diagnostics is enabled in par 12 90 the build in switch is able via Time Domain Reflectometry TDR to detect common cabling problems such as open circuits short circuits and...

Страница 42: ...n Read only Advanced Interface counters from build in switch can be used for low level trouble shooting The parameter shows a sum of port 1 port 2 12 99 Media Counters Range Alignment Errors 0 FCS Err...

Страница 43: ...07 Domain Name max 19 ch Visible string 48 12 08 Host Name max 19 ch Visible string 48 12 09 Physical Address 00 1B 08 00 00 00 Visible string 17 12 1x Ethernet Link Parameters 12 10 Link Status No L...

Страница 44: ...ered Danfoss trademark 44 Data Types Supported by FC 300 Conversion index This number refers to a conversion figure used when writing or reading to parameters Conversion index Conversion factor 67 1 6...

Страница 45: ...message in order to start operation of the frequency converter again A warning on the other hand may appear when a warning condition arises then disappear when conditions return to normal without int...

Страница 46: ...Inverter overloaded 00000400 DC link under voltage 00000800 DC link over voltage 00001000 Short circuit 00002000 Inrush fault 00004000 Mains phase loss 00008000 AMA not OK 00010000 Live zero error 000...

Страница 47: ...nder voltage 00000800 Speed limit 00000800 DC link over voltage 00001000 Reserved 00001000 DC link voltage low 00002000 Reserved 00002000 DC link voltage high 00004000 Reserved 00004000 Mains phase lo...

Страница 48: ...0 Reserved 00000400 Output frequency low 00000800 Reserved 00000800 Brake check OK 00001000 Reserved 00001000 Braking max 00002000 Reserved 00002000 Braking 00004000 Reserved 00004000 Out of speed ran...

Страница 49: ...Relay 123 active 00000040 Start Prevented 00000080 Control ready 00000100 Drive ready 00000200 Quick Stop 00000400 DC Brake 00000800 Stop 00001000 Stand By 00002000 Freeze Output Request 00004000 Free...

Страница 50: ...t Product Code UINT Value of par 12 34 4 Get Revision Struct Value of par 12 33 5 Get Status WORD EIP status word par 12 30 6 Get Serial Number UDINT Serial number 7 Get Product Name String Value of p...

Страница 51: ...uests UINT Number of Forward Close requests rejected due to other reasons 8 Get Connection Timeouts UINT Number of connection timeouts Connection Entry List Struct of NumConnEntries INT Number of conn...

Страница 52: ...emperature 0000 0002 Excessive Device Temperature mar 2240 Earth fault 0000 0004 Short to earth mau 0 unused 0000 0008 No fault 8100 Controlword timeout 0000 0010 Communication mir 2310 Overcurrent 00...

Страница 53: ...ameter Net Reference 6 Get Set Drive Mode USINT Mapping of values from parameter 1 00 7 Get Actual Speed INT See Attribute 22 8 Get Set Reference Speed INT See Attribute 22 18 Get Set Acceleration Tim...

Страница 54: ...rface of the option after the build in switch Instance Attributes Attribute Access Rule Name Data Type Description of Attribute Parameter in drive 1 Get Interface Speed UDINT Interface speed in Mbps e...

Страница 55: ...receive error 12 99 11 Interface Control STRUCT of Configuration for physical interface Control Bits WORD Interface Control Bits 6 Set Forced Interface Speed UINT Speed at which the interface shall b...

Страница 56: ...alue Parameter Attribute From drive 12 Get default value data type described in Attr 5 Generic parameter s default value Parameter Attribute From drive 13 Get Scaling multiplier UINT multiplier for sc...

Страница 57: ...Danfoss trademark 57 3 Get 1st group parameter 000 099 UINT instance number of Parameter Object variable 4 Get 2nd group parameter 100 199 UINT instance number of Parameter Object variable Get UINT v...

Страница 58: ...index of the parameter the value for the attribute Examples fictitious parameters Parameter 0 01 index 0 Class 100 Instance 101 Attribute 100 Parameter 1 00 index 0 Class 101 Instance 100 Attribute 10...

Страница 59: ...object 52 D Danfoss objects 58 Data types 43 E EDS 17 EMC precautions 12 Ethernet 4 14 EtherNet IP 4 14 F FC profile 24 Forward Open 21 H Hardware 5 7 I I O 20 Identity object 50 IGMP 19 Installation...

Отзывы: