7.13.3 Immunity Requirements
The immunity requirements for drives depend on the installation environment. The requirements for the industrial
environment are higher than the requirements for the home and office environment. All Danfoss drives comply with the
requirements for both the industrial and the home/office environment.
To document immunity against burst transient, the following immunity tests have been performed on a drive (with options
if relevant), a shielded control cable, and a control box with potentiometer, motor cable, and motor. The tests were
performed in accordance with the following basic standards. For more details, see
.
•
EN 61000-4-2 (IEC 61000-4-2):
Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
•
EN 61000-4-3 (IEC 61000-4-3):
Incoming electromagnetic field radiation, amplitude modulated simulation of the
effects of radar, radio communication equipment, and mobile communications equipment.
•
EN 61000-4-4 (IEC 61000-4-4):
Burst transients: Simulation of interference brought about by switching a contactor,
relay, or similar devices.
•
EN 61000-4-5 (IEC 61000-4-5):
Surge transients: Simulation of transients brought about by lightning strikes near
installations.
•
EN 61000-4-6 (IEC 61000-4-6):
RF common mode: Simulation of the effect from radio-transmission equipment
joined by connection cables.
Basic standard
Burst
IEC 61000-4-4
Surge
IEC 61000-4-5
ESD
IEC
61000-4-2
Radiated
electro-magnetic field
IEC 61000-4-3
RF common
mode voltage
IEC 61000-4-6
Acceptance criterion
B
B
B
A
A
Line
4 kV CM
2 kV/2
Ω
DM
4 kV/12
Ω
CM
–
–
10 V
RMS
Motor
4 kV CM
4 kV/2
Ω
1)
–
–
10 V
RMS
Control wires
2 kV CM
2 kV/2
Ω
1)
–
–
10 V
RMS
Standard bus
2 kV CM
2 kV/2
Ω
1)
–
–
10 V
RMS
Relay wires
2 kV CM
2 kV/2
Ω
1)
–
–
10 V
RMS
Application/fieldbus options
2 kV CM
2 kV/2
Ω
1)
–
–
10 V
RMS
LCP cable
2 kV CM
2 kV/2
Ω
1)
–
–
10 V
RMS
External 24 V DC
2 V CM
0.5 kV/2
Ω
DM
1 kV/12
Ω
CM
–
–
10 V
RMS
Enclosure
–
–
8 kV AD
6 kV CD
10 V/m
–
Table 7.17 EMC Immunity Form, Voltage Range: 380–480
1) Injection on cable shield.
AD: air discharge; CD: contact discharge; CM: common mode; DM: differential mode.