130BD617.10
1
1
5-pin Connector
Illustration 5.14 Push the 5-pin Connector into Place
5.11 PROFINET
VLT
®
AutomationDrive FC 360 frequency converters
support PROFINET. If PROFINET is needed,
•
Order a new frequency converter on which the
control cassette with PROFINET is pre-installed;
•
Order a control cassette with PROFINET (ordering
number: 132B0257) to replace the standard
control cassette on an existing frequency
converter. In this case, upgrade the software with
MCT-10 Set-up Software. See the
service manual
for the instructions to upgrade the software.
In both cases, ensure that
parameter 15-43 Software Version
is higher than 1.40.
In the package of each control cassette with PROFINET, a
decoupling kit is provided for better mechanical fixation.
Install the decoupling kit after the control casette is
installed.
To install the decoupling kit:
1.
Place the decoupling plate on the control
cassette that is mounted on the frequency
converter, and fasten the plate using 2 screws
(supplied), as shown in
.
Tightening torque 0.7–1.0 Nm (6.2–8.9 in-lb).
1
130BE332.10
1
Screws
Illustration 5.15 Fasten the Plate with Screws
2.
Push the Ethernet cable connectors into the slots
on the control cassette. Place Ethernet cables
between the spring loaded metal clamps, as
shown in
, to establish mechanical
fixation and electrical contact between the cable
and ground.
Commissioning
Quick Guide
MG06A702
Danfoss A/S © 03/2017 All rights reserved.
35
5
5