
-
Select
[155] HW Limit Positive
or
[156]
HW Limit Negative
in parameters 5-10 to
5-16.
-
Enable or disable the software positive
and negative limits in
33-44 Positive
Software Limit Active
and
33-43 Negative
Software Limit Active
respectively.
For both hardware and software limits, set the
positive position in user units in
33-42 Positive
Software Limit
, and negative position in user units
in
33-41 Negative Software Limit
.
•
Maximum allowed velocity
Set the maximum allowed velocity in
32-80
Maximum Allowed Velocity
.
Fault handling
Set the fault behavior in
37-17 Pos. Ctrl Fault Behaviour
.
Fault reasons can be read out from
37-18 Pos. Ctrl Fault
Reason
.
Brake settings
Enable or disable the auto brake control in
37-07 Pos. Auto
Brake Ctrl
. Set brake time in
37-09 Pos. Coast Delay
,
37-11
Pos. Brake Wear Limit
, and
37-12 Pos. PID Anti Windup
.
4.2.3 Defining a User Unit
The frequency converter measures distance in quad-count
(QC) internally. It is possible to define a user unit by using
parameter 32-11 User Unit Denominator
and
parameter 32-12 User Unit Numerator
according to the
following formula:
QC=UU*
32-12 User Unit Numerator
/
32-11 User Unit
Denominator
For example, if the user unit is mm and, based on
measurement, 100.25 mm corresponds to 2000 QC.
2000 QC=100.25 UU, therefore:
QC=(100.25/2000)UU=(401/8000)UU.
Parameter 32-11 User Unit Denominator
and
parameter 32-12 User Unit Numerator
can be set to 8000
and 401 respectively.
4.3 Homing
4.3.1 Selecting Homing Mode
FC 360 provides 3 homing modes. Select the homing
mode in
The 3 modes are described in details as follows.
•
[0] Not forced mode
In this mode, homing is not conducted prior to
positioning. If the
go to home position
command
is issued by digital inputs or PROFIBUS, the
frequency converter sets the current position as
home position.
•
[1] Forced manual mode
In this mode, homing is conducted prior to
positioning. The homing direction is determined
by the sign of
parameter 33-03 Homing Velocity
Find out the current position, and decide whether
it is in the forward or backward direction relative
to the home position.
•
[2] Forced automated mode
In this mode, the homing process starts with the
velocity set in
parameter 33-03 Homing Velocity
and the velocity will be reversed automatically
whenever the hardware position limit is reached
until the home position is found. If the home
position is not found after the hardware limits are
reached twice, the alarm
position ctrl. fault
will be
reported with fault reason
can not find home
position
, which can be viewed in
parameter 37-18 Pos. Ctrl Fault Reason
.
4.3.2 Homing Settings
•
Set the home offset in
•
Set the homing velocity in
.
•
Set the homing ramp time in
parameter 33-03 Homing Velocity
.
•
Select the homing type in
parameter 33-04 Homing Behaviour
.
•
Select 1 digital input as home reference switch
input by setting the corresponding digital input
parameter (5-10 to 5-16) to
[151] Home Ref.
Switch
. Home reference switch input is used for
marking the home position. Switching on
indicates the home position is reached, and
switching off indicates the position is not
reached.
4.3.3 Homing Control
You can control the homing process via digital inputs or
PROFIBUS.
•
Digital inputs
Select a particular digital input as homing switch
by setting the corresponding parameter (5-10 to
5-16) to
[151] Home Ref. Switch
. In forced manual
and automatic modes, switching on the digital
Positioning Control
Application Guide
MG06E102
Danfoss A/S © 11/2014 All rights reserved.
15
4
4