Ground the cable in accordance with grounding
instructions provided.
•
Torque terminals in accordance with the
information provided in
•
Follow the motor manufacturer wiring
requirements
represents line power input, motor, and ground
grounding for basic adjustable frequency drives. Actual
configurations vary with unit types and optional
equipment.
95
130BB920.10
+DC
BR-
B
M
A
I
N
S
L1 L2 L3
91 92 93
RELA
Y 1 RELA
Y 2
99
- LC -
U V
W
MO
TOR
99
Figure 2.8 Example of Motor, Line Power and Ground Wiring
2.4.4 AC Line Power Connection
•
Size wiring based upon the input current of the
Adjustable frequency drive. For maximum wire
sizes, see
10.1 Power-dependent Specifications
.
•
Comply with local and national electrical codes
for cable sizes.
•
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see
•
Depending on the configuration of the
equipment, input power will be connected to the
line power input terminals or the input
disconnect.
•
Ground the cable in accordance with grounding
instructions provided in
•
All adjustable frequency drives may be used with
an isolated input source as well as with ground
reference power lines. When supplied from an
isolated line power source (IT line power or
floating delta) or TT/TN-S line power with a
grounded leg (grounded delta), set
14-50 RFI 1
to
OFF. When off, the internal RFI filter capacitors
between the chassis and the intermediate circuit
are isolated to avoid damage to the intermediate
circuit and to reduce ground capacity currents in
accordance with IEC 61800-3.
2.4.5 Control Wiring
•
Isolate control wiring from high power
components in the adjustable frequency drive.
•
If the adjustable frequency drive is connected to
a thermistor, for PELV isolation, optional
thermistor control wiring must be reinforced/
double insulated. A 24 VDC supply voltage is
recommended.
2.4.5.1 Access
•
Remove access coverplate with a screwdriver. See
•
Or remove front cover by loosening attaching
screws. See
130B
T248.10
Figure 2.9 Control Wiring Access for A2, A3, B3, B4, C3 and C4
Enclosures
Installation
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
2-7
2
2
Содержание VLT AutomationDrive FC 303
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300...
Страница 3: ...Safety VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 7: ...Contents VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG 33 AI 22 VLT is a registered Danfoss trademark 1 1...
Страница 29: ...Installation VLT AutomationDrive Instruction Manual 2 16 MG 33 AI 22 VLT is a registered Danfoss trademark 2 2...
Страница 101: ...Specifications VLT AutomationDrive Instruction Manual 10 26 MG 33 AI 22 VLT is a registered Danfoss trademark 10 10...
Страница 105: ...www danfoss com drives MG33AI22 130R0300 MG33AI22 Rev 2011 05 13...