1-74 Start Speed [RPM]
Range:
Function:
Size
related
*
[0 -
600
RPM]
Set a motor start speed. After the start
signal, the output speed leaps to set value.
Set the start function in
to
[3] Start
speed cw
,
[4] Horizontal operation
, or
[5] VVC
+
/Flux clockwise
, and set a start delay time
in
1-75 Start Speed [Hz]
Range:
Function:
Size
related
*
[ 0 -
500.0
Hz]
This parameter can be used for hoist
applications (cone rotor). Set a motor start
speed. After the start signal, the output
speed leaps to the set value. Set the start
function in
to
[3] Start speed cw
,
[4] Horizontal operation
, or
[5] VVC
+
/Flux clockwise
, and set a start delay
time in
.
1-76 Start Current
Range:
Function:
0
A
*
[ 0 -
par.
1-24 A]
Some motors, for example cone rotor motors,
need extra current/starting speed to disengage
the rotor. To obtain this boost, set the required
current in
. Set
parameter 1-74 Start Speed [RPM]
. Set
to
[3] Start speed cw
or
[4] Horizontal operation
, and set a start delay
time in
.
This parameter can be used for hoist applications
(cone rotor).
3.2.12 1-8* Stop Adjustments
1-80 Function at Stop
Option:
Function:
Select the frequency converter function
after a stop command or after the speed is
ramped down to the settings in
parameter 1-81 Min Speed for Function at
Stop [RPM]
.
[0]
*
Coast
Leaves motor in free mode. The motor is
disconnected from the frequency converter.
[1]
DC hold
Energizes the motor with a DC hold current
(see
parameter 2-00 DC Hold Current
).
[2]
Motor check
Checks if a motor has been connected.
[3]
Pre-
magnetizing
Builds up a magnetic field while the motor
is stopped. This allows the motor to
produce torque quickly at subsequent start
commands (asynchronous motors only). This
1-80 Function at Stop
Option:
Function:
premagnetizing function does not help the
very first start command.
Two different solutions are available to
premagnetize the machine for the first start
command:
•
Start the frequency converter with
a 0 RPM reference and wait 2-4
rotor time constants before
increasing the speed reference.
•
Use the start delay with DC hold:
•
Set
parameter 1-71 Start
Delay
to the required
premagnetizing time (2–4
rotor time constants. See
the time constants
description further in this
section).
•
Set
parameter 1-72 Start
Function
to either
[0] DC
hold
or
[1] DC Brake
.
•
Set the DC hold or DC
brake current magnitude
(
parameter 2-00 DC Hold
Current
or
parameter 2-01 DC Brake
Current
) to be equal to
I_pre-mag = Unom/(1.73
x Xh)
Sample rotor time constants =
(Xh+X2)/(6.3*Freq_nom*Rr)
1 kW = 0.2 s
10 kW = 0.5 s
100 kW = 1.7 s
1000 kW = 2.5 s
[4]
DC Voltage
U0
When the motor is stopped, the
parameter 1-55 U/f Characteristic - U
[0]
defines the voltage at 0 Hz.
[5]
Coast at low
reference
When the motor is stopped, the
parameter 1-55 U/f Characteristic - U
[0]
defines the voltage at 0 Hz.
[6]
Motor check,
alarm
When the motor is stopped, the
parameter 1-55 U/f Characteristic - U
[0]
defines the voltage at 0 Hz.
1-81 Min Speed for Function at Stop [RPM]
Range:
Function:
Size related
*
[0 - 600
RPM]
Set the speed at which to activate
parameter 1-80 Function at Stop
.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
60