0-41 [Off] Key on LCP
Option:
Function:
[2] Password Avoids unauthorized stop. If
parameter 0-41 [Off]
Key on LCP
is included in the
Quick Menu
, then
define the password in
parameter 0-65 Personal
Menu Password
.
0-42 [Auto on] Key on LCP
Option:
Function:
[0] Disabled Avoids accidental start of the frequency converter
in auto-on mode.
[1] Enabled
[2] Password Avoids unauthorized start in auto-on mode. If
parameter 0-42 [Auto on] Key on LCP
is included in
the
Quick Menu
, then define the password in
parameter 0-65 Personal Menu Password
.
0-43 [Reset] Key on LCP
Option:
Function:
[0] Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1] Enabled
[2] Password
Avoids unauthorized resetting. If
parameter 0-43 [Reset] Key on LCP
is included in
the
Quick Menu
, then define the password in
parameter 0-65 Personal Menu Password
.
[7] Enabled
without OFF
Resets the frequency converter without setting
it in Off mode.
[8] Password
without OFF
Resets the frequency converter without setting
it in Off mode. A password is required when
pressing [Reset] (see option
[2] Password
).
0-44 [Off/Reset] Key on LCP
Enable or disable the [Off/Reset] key.
Option:
Function:
[0]
Disabled
[1]
*
Enabled
[2]
Password
0-45 [Drive Bypass] Key on LCP
Press [Off] and select
[0] Disabled
to avoid unintended stop of
the frequency converter. Press [Off] and select
[2] Password
to
avoid unauthorized bypass of the frequency converter. If
parameter 0-45 [Drive Bypass] Key on LCP
is included in the
Quick
Menu
, define the password in
parameter 0-65 Personal Menu
Password
.
Option:
Function:
[0]
Disabled
Select to disable the
key.
[1]
*
Enabled
[2]
Password
3.1.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups
from the frequency converter memory
to the LCP memory.
[2]
All from LCP
Copies all parameters in all set-ups
from the LCP memory to the frequency
converter memory.
[3]
Size indep. from
LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to program
several frequency converters with the
same function without disturbing
motor data.
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
[7]
Data from LCP to
DYN
[9]
Safety Par. from
LCP
[10] Delete LCP copy
data
Use to delete the copy after the
transfer is complete.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy to set-
up 1
Copies all parameters in the present
programming set-up (defined in
) to set-up 1.
[2]
Copy to set-
up 2
Copies all parameters in the present
programming set-up (defined in
) to set-up 2.
[3]
Copy to set-
up 3
Copies all parameters in the present
programming set-up (defined in
) to set-up 3.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
39