3.27.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/7. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-25 Term. X48/7 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/7. Set the temperature
limits in
parameter 35-26 Term. X48/7 Low Temp. Limit
and
parameter 35-27 Term. X48/7 High Temp. Limit
.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-26 Term. X48/7 Low Temp. Limit
Range:
Function:
Size related
*
[ -50 - par.
35-27 ]
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
35-27 Term. X48/7 High Temp. Limit
Range:
Function:
Size related
*
[ par. 35-26 -
204 ]
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
3.27.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-35 Term. X48/10 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/10. Set the
temperature limits in
parameter 35-36 Term. X48/10 Low Temp.
Limit
/
parameter 35-37 Term. X48/10 High Temp. Limit
Option:
Function:
[0]
*
Disabled
[1]
Enabled
35-36 Term. X48/10 Low Temp. Limit
Range:
Function:
Size related
*
[ -50 - par.
35-37 ]
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
35-37 Term. X48/10 High Temp. Limit
Range:
Function:
Size related
*
[ par. 35-36 -
204 ]
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
3.27.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
Function:
4 mA
*
[ 0 - par.
35-43 mA]
Enter the current (mA) that corresponds to
the low reference value, set in
parameter 35-44 Term. X48/2 Low Ref./Feedb.
Value
. The value must be more than 2 mA to
activate the live zero timeout function in
parameter 6-01 Live Zero Timeout Function
35-43 Term. X48/2 High Current
Range:
Function:
20 mA
*
[ par. 35-42 -
20 mA]
Enter the current (mA) that corresponds
to the high reference value (set in
parameter 35-45 Term. X48/2 High Ref./
Feedb. Value
).
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the reference or
feedback value (in RPM,
Hz, bar, and so on) that
corresponds to the voltage
or current set in
parameter 35-42 Term.
X48/2 Low Current
.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
246