Enclosure size
415 V
IEC
1)
480 V
UL
2)
600 V
UL
2)
D6h
100000 A
100000 A
100000 A
D8h (excluding N250 380-500V model)
100000 A
100000 A
100000 A
D8h (N250 380-500V model only)
100000 A
Contact Danfoss
Not applicable
Table 10.14 D6h and D8h Drives Supplied with a Disconnect and Contactor
1)
With gL/gG fuses: 425A maximum fuse size for D6h, and 630A maximum fuse size for D8h.
2)
With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h.
Enclosure size
415 V
480 V
600 V
690 V
D6h
120000 A
100000 A
65000 A
70000 A
D8h
100000 A
100000 A
42000 A
30000 A
Table 10.15 D6h and D8h Drives Supplied with a Circuit Breaker Only
10.8 Fastener Tightening Torques
Apply the correct torque when tightening fasteners in the locations that are listed in
. Too low or too high torque
when fastening an electrical connection results in a bad electrical connection. To ensure correct torque, use a torque
wrench.
Location
Bolt size
Torque [Nm (in-lb)]
Mains terminals
M10/M12
19 (168)/37 (335)
Motor terminals
M10/M12
19 (168)/37 (335)
Ground terminals
M8/M10
9.6 (84)/19.1 (169)
Brake terminals
M8
9.6 (84)
Load sharing terminals
M10/M12
19 (168)/37 (335)
Regeneration terminals (Enclosures D1h/D2h)
M8
9.6 (84)
Relay terminals
_
0.5 (4)
Door/panel cover
M5
2.3 (20)
Gland plate
M5
2.3 (20)
Heat sink access panel
M5
3.9 (35)
Serial communication cover
M5
2.3 (20)
Table 10.16 Fastener Torque Ratings
Specifications