4.1.2 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up
procedure using LCP 102 (read
from left to right). The example applies to open loop applications.
Press
Quick
Menu
Q2 Quick Menu
OK
OK
Set language
Parameter 1-20 Motor Power [kW]
OK
Set Motor nameplate power
1-22 Motor Voltage
OK
Set Nameplate voltage
Parameter 1-23 Motor Frequency
OK
Set Nameplate frequency
1-24 Motor Current
OK
Set Nameplate current
1-25 Motor Nominal Speed
OK
Set Nameplate speed in RPM
5-12 Terminal 27 Digital Input
OK
If terminal default is
Coast
inverse
it is possible to change
this setting to
No function
. No
connection to terminal 27 is
then needed for running AMA
1-29 Automatic Motor Adaptation
(AMA)
OK
Set desired AMA function.
Enable complete AMA is
recommended
Parameter 3-02 Minimum Reference
OK
Set the minimum speed of the
motor shaft
Parameter 3-03 Maximum Reference
OK
Set the maximum speed of the
motor shaft
Parameter 3-41 Ramp 1 Ramp Up
Time
OK
Set the ramping up time with
reference to synchronous
motor speed, n
s
Parameter 3-42 Ramp 1 Ramp Down
Time
OK
Set the ramping down time
with reference to synchronous
motor speed, n
s
3-13 Reference Site
OK
Set the site from where the
reference must work
Table 4.1 Quick Set-up Procedure
How to Programme
VLT
®
Automation Drive FC 300 Operating Instructions
82
MG33U402 - Rev. 2013-12-16
4
4