
1.
1.
-
5.2.2.2.2 PM Parking
This function is the recommended selection for applications where the motor is rotating at slow speed, for example windmilling in
fan applications.
Parameter 2-06 Parking Current
and
parameter 2-07 Parking Time
can be adjusted. Increase the factory setting of
these parameters for applications with high inertia.
To activate parking, select
[1] Parking
in
parameter 1-70 Start Mode
.
5.2.2.2.3 Application-specific Adjustment when Running VVC+ with PM Motors
VVC+ is the most robust control mode. In most situations, it provides optimum performance without further adjustments. Run a
complete AMA for best performance.
Start the motor at nominal speed. If the application does not run well, check the VVC+ PM settings. See recommendations for vari-
ous applications in
Table 68: Recommendations for Various Applications
Application
Settings
Low-inertia applications
I
Load
/I
Motor
<5
Increase
parameter 1-17 Voltage Filter Time Const.
by factor 5–10.
Reduce
parameter 1-14 Damping Gain
.
Reduce
parameter 1-66 Min.Current at Low Speed
(<100%).
Low-inertia applications
50>I
Load
/I
Motor
>5
Keep the default values.
High-inertia applications
I
Load
/I
Motor
>50
Increase
parameter 1-14 Damping Gain
,
parameter 1-15 Low Speed Filter Time Const.
, and
parame-
ter 1-16 High Speed Filter Time Const
.
High load at low speed <30%
(rated speed)
Increase
parameter 1-17 Voltage filter time const
. Increase
parameter 1-66 Min. Current at Low
Speed
to adjust the starting torque. 100% current provides nominal torque as starting torque.
This parameter is independent of
parameter 30-20 High Starting Torque Time [s]
and
parameter
30-21 High Starting Torque Current [%]
). Working at a current level higher than 100% for a pro-
longed time can cause the motor to overheat.
If the motor starts oscillating at a certain speed, increase
parameter 1-14 Damping Gain
. Increase the value in small steps. Depending
on the motor, this parameter can be set to 10–100% higher than the default value.
Application-specific adjustment when running flux
Flux control principle is the preferred control principle for optimum shaft performance in dynamic applications. Perform an AMA
because this control mode requires precise motor data. Depending on the application, further adjustments may be required.
See
5.2.2.1 Asynchronous Motor Setup
for application-specific recommendations.
5.2.2.3 SynRM Motor Setup with VVC+
This section describes how to set up a SynRM motor with VVC+.
N O T I C E
The SmartStart wizard covers the basic configuration of SynRM motors.
5.2.2.3.1 SynRM Initial Programming
Procedure
Select
[5] Sync. Reluctance
in
parameter 1-10 Motor Construction
to activate SynRM motor operation.
5.2.2.3.2 SynRM Programming Motor Data
After performing the initial programming steps, the SynRM motor-related parameters in
parameter groups 1-2* Motor Data
,
1-3* Adv.
Motor Data
, and
1-4* Adv. Motor Data II
are active. Find the required motor data on the motor nameplate and in the motor data
sheet.
Procedure
Program in the following order:
AU275636650261en-000101 / 130R0334 | 71
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide