![Danfoss VLT AutomationDrive FC 300 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-300/vlt-automationdrive-fc-300_programming-manual_3500006032.webp)
3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on the
LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
*
Disabled
No effect when [Hand on] is pressed. Select
[0] Disabled to avoid accidental start of the
drive in
Hand on
mode.
[1]
*
Enabled
The LCP switches to
Hand on
mode directly
when [Hand on] is pressed.
[2]
Password
After pressing [Hand on] a password is
required. If
is in
included in
My Personal Menu
, define the
password in
Otherwise define the password in
0-60 Main
Menu Password
.
[3]
Hand Off/On
When [Hand on] is pressed once, the LCP
switches to
Off
mode. When pressed again,
the LCP switches to
Hand on
mode.
[4]
Hand Off/On w.
Passw.
Same as [3] but a password is required (see
[2]).
[9]
Enabled, ref = 0
0-41 [Off] Key on LCP
Option:
Function:
[0]
*
Disabled Avoids accidental stop of the frequency
converter.
[1]
*
Enabled
[2]
Password Avoids unauthorised stop. If
is
included in the Quick Menu, then define the
password in
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
*
Disabled Avoid accidental start of the frequency converter
in Auto mode.
[1]
*
Enabled
[2]
Password Avoids unauthorised start in Auto mode. If
is included in the Quick
Menu, then define the password in
.
0-43 [Reset] Key on LCP
Option:
Function:
[0]
*
Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
*
Enabled
[2]
Password
Avoids unauthorised resetting. If
is included in the
Quick Menu, then define the password in
.
0-43 [Reset] Key on LCP
Option:
Function:
[7]
Enabled
without OFF
Resets the drive without setting it in
Off
mode.
[8]
Password
without OFF
Resets the drive without setting it in
Off
mode. A password is required when
pressing [Reset] (see [2]).
3.2.6 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups
from the frequency converter memory
to the LCP memory.
[2]
All from LCP
Copies all parameters in all set-ups
from the LCP memory to the frequency
converter memory.
[3]
Size indep. from
LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
programme several frequency
converters with the same function
without disturbing motor data.
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
[7]
Data from LCP to
DYN
This parameter cannot be adjusted while the motor is
running.
Parameter Descriptions
FC 300 Programming Guide
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
31