3.5.2 EMC Test Results
The following test results have been obtained using an adjustable frequency drive (with options if relevant), a shielded
control cable, a control box with potentiometer, as well as a motor and motor shielded cable.
RFI filter type
Conducted Emission
Radiated Emission
Standards and
requirements
EN 55011
Class B
Housing, trades
and light
industries
Class A
group 1
Industrial
environment
Class A
group 2
Industrial
environment
Class B
Housing, trades
and light
industries
Class A group 1
Industrial
environment
EN/IEC 61800-3
Category C1
First
environment
home and
office
Category C2
First
environment
home and
office
Category C3
Second
environment
Industrial
Category C1
First environment
home and office
Category C2
First environment
home and office
H2
FC 302
125–1075 hp [90–800
kW] 380–500 V
No
No
500 ft [150 m]
No
No
125–1600 hp [90–1200
kW] 525–690 V
No
No
500 ft [150 m]
No
No
H4
FC 302
125–1075 hp [90–800
kW] 380–500 V
No
500 ft [150 m] 500 ft [150 m]
No
Yes
125–450 hp [90–315
kW] 525–690 V
No
100 ft [30 m]
500 ft [150 m]
No
No
Table 3.14 EMC Test Results (Emission and Immunity)
WARNING
This type of power drive system is not intended to be used on a low-voltage public network that supplies domestic
premises. Radio frequency interference is expected if used on such a network, and supplementary mitigation measures
may be required.
Product Introduction
Design Guide
48
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
3
3
Содержание VLT AutomationDrive FC 300
Страница 2: ......