0-04 Operating State at Power-up (Hand)
Option:
Function:
(applied by [Hand On/Off]) as before the
frequency converter was powered down.
[1]
*
Forced stop,
ref=old
Restarts the frequency converter with a
saved local reference, after mains voltage
reappears and after pressing [Hand On].
[2]
Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
3.2.2 0-1* Set-up Operations
Define and control the individual parameter setups.
The frequency converter has four parameter setups that
can be programmed independently of each other. This
makes the frequency converter very flexible and able to
solve advanced control functionality problems, often
saving the cost of external control equipment. For example
these can be used to program the frequency converter to
operate according to one control scheme in one setup
(e.g. motor 1 for horizontal movement) and another
control scheme in another setup (e.g. motor 2 for vertical
movement). Alternatively they can be used by an OEM
machine builder to identically program all their factory
fitted frequency converters for different machine types
within a range to have the same parameters and then
during production/commissioning simply select a specific
setup depending on which machine the frequency
converter is installed on.
The active setup (i.e. the setup in which the frequency
converter is currently operating) can be selected in
and is displayed in the LCP. Using Multi
set-up it is possible to switch between setups with the
frequency converter running or stopped, via digital input
or serial communication commands. If it is necessary to
change setups whilst running, ensure
is programmed as required. Using
it is possible to edit parameters within any of the setups
whilst continuing the frequency converter operation in its
Active Setup which can be a different setup to that being
edited. Using
it is possible to copy
parameter settings between the setups to enable quicker
commissioning if similar parameter settings are required in
different setups.
0-10 Active Set-up
Option:
Function:
Select the set-up to control the frequency
converter functions.
[0]
Factory setup Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a
known state.
0-10 Active Set-up
Option:
Function:
[1]
*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
are the four
separate parameter set-ups within which all
parameters can be programmed.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-up
Remote selection of set-ups using digital
inputs and the serial communication port.
This set-up uses the settings from
. Stop the frequency
converter before making changes to open-
and closed loop functions
Use
to copy a set-up to one or all other
set-ups. Stop the frequency converter before switching
between set-ups where parameters marked ‘not
changeable during operation’ have different values. To
avoid conflicting settings of the same parameter within
two different set-ups, link the set-ups together using
. Parameters which are ‘not
changeable during operation’ are marked FALSE in the
parameter lists in
.
0-11 Edit Set-up
Option:
Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups.
[0]
Factory setup Cannot be edited but it is useful as a data
source to return the other set-ups to a
known state.
[1]
*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
can be edited
freely during operation, independently of
the active set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up Can also be edited during operation. Edit
the chosen set-up from a range of sources:
LCP, FC RS-485, FC USB or up to five fieldbus
sites.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
25
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......