
3.18 Parameters: 17-** Motor Feedb.
Option
Additional parameters to configure the Encoder (MCB 102)
or the Resolver (MCB 103) Feedback Option.
3.18.1 17-1* Inc. Enc. Interface
Parameters in this group configure the incremental
interface of the MCB 102 option. Note that both the
incremental and absolute interfaces are active at the same
time.
NOTE
These parameters cannot be adjusted while the motor is
running.
17-10 Signal Type
Select the incremental type (A/B channel) of the encoder in use.
Find the information on the encoder data sheet.
Select
[0] None
if the feedback sensor is an absolute encoder
only.
Option:
Function:
[0]
None
[1]
*
RS422 (5V TTL)
[2]
Sinusoidal 1Vpp
17-11 Resolution (PPR)
Range:
Function:
1024
*
[10 - 10000 ] Enter the resolution of the incremental
track, i.e. the number of pulses or periods
per revolution.
3.18.2 17-2* Abs. Enc. Interface
Parameters in this group configure the absolute interface
of the MCB 102 option. Note that both the incremental
and absolute interfaces are active at the same time.
17-20 Protocol Selection
Select
[1] HIPERFACE
if the encoder is absolute only.
Select
[0] None
if the feedback sensor is an incremental encoder
only.
Option:
Function:
[0]
*
None
[1]
HIPERFACE
[2]
EnDat
[4]
SSI
NOTE
This parameter cannot be adjusted while the motor is
running.
17-21 Resolution (Positions/Rev)
Select the resolution of the absolute encoder, i.e. the number of
counts per revolution.
The value depends on setting in
Range:
Function:
Size related
*
[ 4. - 131072. ]
NOTE
This parameter cannot be adjusted while the motor is
running.
17-24 SSI Data Length
Range:
Function:
13
*
[13 - 25 ] Set the number of bits for the SSI telegram.
Choose 13 bits for single-turn encoders and 25
bits for multi-turn encoder.
17-25 Clock Rate
Range:
Function:
Size related
*
[ 100 - 0 kHz] Set the SSI clock rate. With long
encoder cables the clock rate must
be reduced.
17-26 SSI Data Format
Option:
Function:
[0]
*
Gray code
[1]
Binary code Set the data format of the SSI data. Choose
between Gray or Binary format.
17-34 HIPERFACE Baudrate
Select the baud rate of the attached encoder.
The parameter is only accessible when
is
set to
[1] HIPERFACE
.
Option:
Function:
[0]
600
[1]
1200
[2]
2400
[3]
4800
[4]
*
9600
[5]
19200
[6]
38400
NOTE
This parameter cannot be adjusted while the motor is
running.
3.18.3 17-5* Resolver Interface
Parameter group 17-5* is used for setting parameters for
the MCB 103 Resolver Option.
Usually the resolver feedback is used as motor feedback
from Permanent Magnet motors with
set to Flux with motor feedback.
Resolver parameters cannot be adjusted while the motor is
running.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
150
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......