View the torque value with sign, applied to the motor shaft. Some motors supply more than 160% torque. Therefore, the minimum
value and the maximum value depend on the maximum motor current as well as the motor used. This specific readout has been
adapted to be able to show higher values than the standard readout in
parameter 16-16 Torque [Nm]
.
4.16.3 16-3* Drive Status
Parameter 16-30 DC Link Voltage
Table 599: Parameter 16-30 DC Link Voltage
16-30 DC Link Voltage
Default Value: 0 V
Parameter Type: Range, 0 - 10000 V
Setup: All set-ups
Conversion Index: 0
Data Type: Uint16
Change during operation: False
View a measured value. The value is filtered with a 30 ms time constant.
Parameter 16-31 System Temp.
Table 600: Parameter 16-31 System Temp.
16-31 System Temp.
Default Value: 0 °C
Parameter Type: Range, -128 - 127 °C
Setup: All set-ups
Conversion Index: 100
Data Type: Int8
Change during operation: True
Shows the highest internal system temperature. In the smaller enclosure sizes (A–C), the system temperature matches the control
card temperature measurement in
parameter 16-39 Control Card Temp
. In the larger enclosure sizes (D–F), the system temperature is
the highest temperature measured on hardware components with temperature sensors, for example, the power card(s).
Parameter 16-32 Brake Energy /s
Table 601: Parameter 16-32 Brake Energy /s
16-32 Brake Energy /s
Default Value: 0 kW
Parameter Type: Range, 0 - 10000 kW
Setup: All set-ups
Conversion Index: 0
Data Type: Uint32
Change during operation: False
View the brake power transmitted to an external brake resistor, stated as an instant value.
Parameter 16-33 Brake Energy Average
Table 602: Parameter 16-33 Brake Energy Average
16-33 Brake Energy Average
Default Value: 0 kW
Parameter Type: Range, 0 - 10000 kW
Setup: All set-ups
Conversion Index: 0
Data Type: Uint32
Change during operation: False
View the brake power transmitted to an external brake resistor. The mean power is calculated on an average level based on the
selected time period within
parameter 2-13 Brake Power Monitoring
.
Parameter 16-34 Heatsink Temp.
Table 603: Parameter 16-34 Heatsink Temp.
16-34 Heatsink Temp.
Default Value: 0 °C
Parameter Type: Range, 0 - 255 °C
Setup: All set-ups
Conversion Index: 100
Data Type: Uint8
Change during operation: False
View the drive heat sink temperature. The cutout limit is 90 ±5 °C (194 ±9 °F), and the motor cuts back in at 60 ±5 °C (140 ±9 °F).
AU373327181955en-000101 / 130R1208
306 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide